BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The XP6-MA Six Zone Interface Module is intended for use in an intelligent
alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
A list of compatible two-wire System Sensor Smoke detectors for use with the
XP6-MA is available on the System Sensor website at www.systemsensor.com.
Included:
(5) 1 x 4 Terminal Blocks (2) 1.25" Stand offs (3) Shunts
(4) Machine Screws (2) Nuts (1) Long Power Supply Jumper
(6) 3.9k Ohm End of Line Resistors
C0202-00
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
1
I56-1806-010
7/1/2022
XP6-MA Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage:
15-32VDC
Stand-By Current:
2.3 mA @ 24 V
Alarm Current:
40 mA (assumes all six LEDs solid on)
Temperature Range:
32ºF to 120ºF ( 0ºC to 49ºC)
Humidity:
10 to 93% Non-condensing
Dimensions:
6.8˝H x 5.8˝W x 1.25˝D
Accessories:
CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets
Wire Gauge:
12-18 AWG
Maximum IDC Wiring Resistance:
25 Ohms
External Power Supply Voltage:
Regulated 24 VDC
Ripple Voltage:
0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage:
18-28 volts power limited
Frequency:
DC
Alarm Current:
90mA per circuit
Standby Current 6 circuits:
42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28 VDC
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Notifier system control panel (list available from Notifier).
COMPONENTS
Following are descriptions of the XP6-MA mounting frameworks. There are
two mounting options for XP6-MA modules:
• Up to six XP6-MA modules can be installed on a CHS-6 in a CAB-3
Series, CAB-4 Series or BB-25 cabinet
• One or two XP6-MA modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount XP6-MA modules in a BB-25, CAB-3 or
CAB-4 Series cabinet. It accommodates up to six XP6-MA modules in a single
cabinet row three modules wide and two modules deep.
FIGURE 1. CHS-6 CHASSIS
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
C0236-01
The BB-XP cabinet has a built-in chassis that will accommodate one or two
XP6-MA modules.
FIGURE 2. BB-XP CABINET
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
B
A
S
E
A
D
D
R
E
S
S
A
D
D
R
E
S
S
D
IS
A
B
LE
N
O
N
E
ON
E
TW
O
THR
EE
0
1
2 3 4 5 6
7
8
9
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
B
A
S
E
A
DDRE
S
S
A
DD
R
E
S
S
DI
S
A
B
LE
NONE
ON
E
TW
O
THR
EE
C0234-00
I56-1806-0
10
INSTALLATION AND MAINTENANCE INSTRUCTIONS
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161