SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
81
Master Programming Level
Programming
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 75, for a
detailed description of this feature. Pressing
1
while viewing System Setup Screen #2 will cause
the display to toggle to
Trouble Rem Yes
, which enables this feature. Each press of the
1
key will
cause the display to toggle between
Trouble Rem Yes
and
Trouble Rem No
.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for more
than 24 hours will cause the FACP to resound the trouble sounder.
Canadian Option
Pressing
2
while viewing System Setup Screen #2 will configure the FACP to comply with Cana-
dian requirements. The display will change to
Canadian Opt. On
. Each press of the
2
key will
cause the display to toggle between
Canadian Opt. On
and
Canadian Opt. Off.
The factory default
setting is
Canadian Opt. Off.
For Canadian applications, remote annunciation must be done using the secondary ANN-BUS.
The Canadian Options configures the FACP with the following as required by Canada:
•
The following zone type codes are not available:
non-latching supervisory
non-latching drill
process monitor (latching or non-latching)
hazard
tornado
medical alert
combo autoresettable
•
The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals
will be turned off after 20 minutes of activation
•
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
label, located on the FACP backbox door
Charger Disable
Pressing
3
while viewing System Setup Screen #2 will allow the programmer to enable or disable
the onboard battery charger. If an external battery charger is being used, the onboard battery char-
ger must be disabled. Each press of the
3
key will toggle between
Chrgr Disable No
and
Chrgr
Disable Yes
.
3.5.5 Option Modules
Options available for the FACP include annunciators, printer connection for acquiring hardcopy
printouts of panel data and onboard DACT.
Pressing
2
while viewing Programming Screen #2 will display the following screen:
SYSTEM SETUP
1=TROUBLE REMIND NO
2=CANADIAN OPTION OFF
3=CHARGR DISABLE NO
System Setup Screen #2
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES
3=HISTORY
Programming Screen #2
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT