70
SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
Programming
Master Programming Level
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to
305.
4. Press the
Enter
key to store the information.
3.5.2 NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configured by pressing
2
while viewing Programming Screen #2. The following screens will be displayed:
The Notification Appliance Circuits can be configured independently by pressing
1
for NAC 1,
2
for NAC 2,
3
for NAC 3, or
4
for NAC 4.
To program an NAC circuit, press the number corresponding to the NAC to be programmed. The
following screens will be displayed for each selection:
Enabled
Pressing
1
while viewing NAC Screen #1 will cause the display to change to
Enabled No
. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the
1
key
will cause the display to toggle between
Enabled Yes
and
Enabled No
.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is enabled.
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
NACS
1=NAC 1 3=NAC 3
2=NAC 2 4=NAC 4
NAC Selection Screen
NAC #
1=ENABLED YES
2=CODING
STEADY
NAC Screen #1
NAC Screen #2
NAC #
1=SILENCE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
NAC #
1=ENABLED
2=CODING
STEADY
NAC Screen #1