SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
23
Telephone Requirements and Warnings
Product Description
feet away from the control panel. Note that when using an NFS-LBB for housing the charger and
batteries greater than 26AH, multiple NFS-LBBs are required. Refer to the
CHG-120 Manual
for
additional information.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly
from most IBM compatible personal computers (PC), running Windows
®
XP (or newer). FACP
program files can also be created and stored on the PC and then downloaded later to the control
panel. The Windows-based Programming Utility, PS-Tools, and its on-line help file are available
for download from www.magni-fire.com. A standard USB cable with male-A to male-B connec-
tors, which must be purchased separately, is required for local connection of the PC to the USB port
J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud
(or faster) modem.
Important:
Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to “Remote Download” on page 132). Remote interrogation of panel pro-
gramming, history logs, detector status, etc., is possible without enabling the remote download
option.
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line as determined by the total RENs,
contact the telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty
information, please contact:
Manufacturer:
Notifier
12 Clintonville Road
Northford, CT 06472
(203) 484-7161
Product Model Number:
SFP-5UD/SFP-10UD
FCC Registration Number:
1W6AL00B10UD
Ringer Equivalence:
0.0B
Important!
The DACT must not be used to dial a phone number that is call-forwarded.
This equipment complies with Part 68 of the FCC rules and the requirements adopted by
the ACTA. On the inside of the FACP door is a label that contains, among other
information, a product identifier in the format
US:AAAEQ##TXXXX
. If requested, this
number must be provided to the telephone company.