
98
SCS Series Manual —
P/N 15712:L 7/18/16
The SCS⁄SCE
Building-Specific Operation and Programming Examples
After the dipswitch settings have been determined, an EIA-485 device address for each SCS must be determined. As stated before, there are
32 available addresses. So, if no other EIA-485 devices are present on the data line (such as annunciators) the maximum number of SCS⁄SCE
pairs allowed is 32. For our example, we only need three available addresses. Let us assume that addresses 5, 6, and 7 are available. As
shown in Table 3.4 and Figure 3.4, set the dipswitches and addresses of each SCS.
The next step is to categorize all protocol points as needed, unneeded, or unused, as discussed in Section 2.4.2. Using the bottom portion of
worksheet 2 as a guide, our example for the SCS at address 5 would look like the following:
For AM2020/AFP1010 only: After categorizing all protocol points, the software type IDs can be selected as discussed in Section 2.4.2. All
protocol points that are needed get assigned software type IDs from Table 3.13. All protocol points that are unneeded do not get a software
type ID and do not get programmed into FACP memory. All protocol points that are unused get assigned the software type ID ACON. Use
worksheet 2 in Appendix B to organize this information.
Installation
At this point, all the preliminary design work is complete. The next step is to install all control modules and monitor modules on the required
devices, as shown in Section 5 “Ratings and Wiring Diagrams”, and install the SCS⁄SCE pairs as described in Section 2.2. Once the installa-
tion of all fans, dampers, control modules, monitor modules, SCSs, and SCEs is complete, the FACP requires additional programming for
smoke control.
Programming (AM2020/AFP1010 Example)
Programming SCS annunciator addresses, linking annunciator points with control or monitor modules, assigning control and monitor Type
IDs, and creating control-by-event equations to obtain desired fan and damper activity, are the steps required to complete the smoke control
setup. Refer to Programming in Section 2.4 for descriptions of the various programming processes. Following is a step-by-step description of
AM2020/AFP1010 programming for this example.
The first step to programming the FACP for smoke control is to define each SCS address in FACP memory. Refer to Section 2.4.1, EIA-485
Device Addressing, for instructions. SCS addresses 5, 6, and 7 must to be entered for this example.
The next step is to program all EIA-485 protocol points, including software type IDs. By referencing the worksheets, all the information nec-
essary is close at hand.
Point Assignments:
classification
type ID
Point Assignments:
classification
type ID
1
(CON
ON⁄OP
)
needed
_______
17
(CON
ON⁄OP
)
unneeded
_______
2
(CON
OFF⁄CL
)
unneeded
_______
18
(CON
OFF⁄CL
)
needed
_______
3
(VER
ON⁄OP
)
needed
_______
19
(VER
ON⁄OP
)
unneeded
_______
4
(VER
OFF⁄CL
)
unneeded
_______
20
(VER
OFF⁄CL
)
needed
_______
5
(CON
ON⁄OP
)
needed
_______
21
(CON
ON⁄OP
)
unused
_______
6
(CON
OFF⁄CL
)
unneeded
_______
22
(CON
OFF⁄CL
)
unused
_______
7
(VER
ON⁄OP
)
needed
_______
23
(VER
ON⁄OP
)
unused
_______
8
(VER
OFF⁄CL
)
unneeded
_______
24
(VER
OFF⁄CL
)
unused
_______
9
(CON
ON⁄OP
)
needed
_______
25
(CON
ON⁄OP
)
unused
_______
10
(CON
OFF⁄CL
)
unneeded
_______
26
(CON
OFF⁄CL
)
unused
_______
11
(VER
ON⁄OP
)
needed
_______
27
(VER
ON⁄OP
)
unused
_______
12
(VER
OFF⁄CL
)
unneeded
_______
28
(VER
OFF⁄CL
)
unused
_______
13
(CON
ON⁄OP
)
needed
_______
29
(CON
ON⁄OP
)
unused
_______
14
(CON
OFF⁄CL
)
unneeded
_______
30
(CON
OFF⁄CL
)
unused
_______
15
(VER
ON⁄OP
)
needed
_______
31
(VER
ON⁄OP
)
unused
_______
16
(VER
OFF⁄CL
)
unneeded
_______
32
(VER
OFF⁄CL
)
unused
_______