SCS Series Manual —
P/N 15712:L 7/18/16
201
Appendix B: Miscellaneous Information
B.1 NFS-320 and NFS2-640 Control-By-Event
Your fire alarm control panel provides control-by-event (CBE) programming for the Smoke Control System. Logic and Trouble Equations
can define complex relationships between input and output devices. Program your NFS-320 or NFS2-640 according to the instructions in the
panel’s Listing Document. For additional documentation on this product, go to http://esd.notifier.com. This additional documentation may be
used as a reference only.
B.2 NFS2-3030 Control-By-Event
Your fire alarm control panel provides control-by-event (CBE) programming for the Smoke Control System. Logic and Trouble Equations
can define complex relationships between input and output devices. Program your NFS2-3030 according to the instructions in the panel’s
Listing Document. For additional documentation on this product, go to http://esd.notifier.com. This additional documentation may be used as
a reference only.
B.3 NCA-2 Operation
NCA-2 V21 supports logic equations that can be used with SCS-8/8L V4.0. See the NCA-2 Manual for instructions
B.4 Appendix D SCS⁄SCE Worksheets
The Worksheets provided in the section should be used to organize information required for the design of a smoke control system. These
worksheets should be kept as originals and copies should be made as needed.
Worksheet One is used to determine the number of fans and dampers that will be used for smoke control, their capabilities, and associated
switch group type. The information from this sheet will help the designer configure the switch group types to the SCS. Once the configura-
tion of each SCS⁄SCE is determined, the information on Worksheet Two can be completed.
Worksheet Two is used to organize information for each SCS or SCS⁄SCE pair. The majority of this information will be used when program-
ming the FACP for smoke control.
Worksheet Three is used to organize information associated with the control and monitor modules that will be used for smoke control. This
information should be organized and completed prior to beginning programming of the FACP.
B.5 Compatibility with Other Systems
XLS3000 System
All smoke control modules described in this book are XLS3000 system compatible. Installation, programming and operation are as
described in this manual. For programming, refer to the NFS2-3030 programming sections in this manual.