
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
143
NFPA 72 Auxiliary Fire Alarm System
NFPA Standard-Specific Requirements
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP30 on the RP-2002 main circuit board to supervise placement of 4XTM module and
circuit.
3.
Cut JP24 on the RP-2002 main circuit board to enable FACP Supervisory relay.
4.
Refer to “4XTM Municipal Box Transmitter Option Module” on page 33 for detailed
information.
FIRE
Gamewell Model M34-56 Local
Energy Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
Municipal Box Circuit
+
_
-
4XTM
Figure C.2 Municipal Box Connected to 4XTM Transmitter Module
Summary of Contents for NOTIFIER RP-2002C
Page 158: ...Cut along dotted line ...