FACP Configuration Templates
Template 12: Agent/Waterflow - Single Detector
B.12 Template 12: Agent/Waterflow - Single Detector
Table Legend:
*
= shows relationship only, will not activate a release circuit
X
= direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit after any applicable delays).
X
r
= release stage output where X indicates a direct correlation between Input Zone and Output
Circuit (input zone activation will activate the corresponding output circuit) and
r
indicates that the
output circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to
“Release Stage/NAC Operation” on page 85).
Input Zone Types:
•
Zone 1 = circuit with type code of 2-wire smoke
•
Zone 2 = circuit with type code of 2-wire smoke
•
Zone 3 = circuit with type code Manual Release/Abort Switch Combo - activation of the
Manual Release will cause an immediate agent release; Abort Switch - programmed for UL
Abort Type operation (refer to “Abort Type” on page 65)
•
Zone 4 = circuit with type code of Discharge Pressure Switch
•
Zone 5 = circuit with type code of Waterflow
•
Zone 6 = circuit with type code of Supervisory
Output Circuit Types:
•
Output 1 = Release Circuit 1 - Supervised for shorts
•
Output 2 = Release Circuit 2 - Supervised for shorts
•
Output 3 = Alarm NAC - silenceable, steady on
•
Output 4 = Release Stage Coded - nonsilenceable, programmed Release Stage Coded operation
for Release Circuit 1 (refer to“Cross-Zone for Release Circuit 1 or Release Circuit 2:” on
page 61)
ANN-BUS
•
Enabled = Yes
•
Address 1: ANN-RLY
Timers
•
Pre-Discharge Delay: Release 1 - set for 30 seconds; Release 2 - set for 0 seconds
•
Discharge: Release 1 - set for Always On; Release 2 - set for Always On
•
Waterflow Delay Timer - set for 90 seconds
•
AC Loss Delay Timer - set for 2 hours
Template 12: Agent/Waterflow - Single Detector
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE
SMOKE
2-WIRE
SMOKE
MANUAL
RELEASE/AB
ORT SW.
COMBO
DISCHARGE
PRESSURE
WATERFLOW
SUPERVISORY
#1 RELEASE CIRCUIT 1
X
X
X
X*
#2 RELEASE CIRCUIT 2
X
X
X
X*
#3 ALARM NAC
X
X
X
X
X
#4 RELEASE STAGE
CODED
Xr
Xr
Xr
Xr