56
RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
Programming
Master Programming Level
1.
The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3.
2.
With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display
ROOM_304
. The cursor automatically jumps from the first to the last letter of the
Noun field.
3.
With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to
305.
4.
Press the Enter key to store the information.
3.5.3 Output Circuits
The options for the Output Circuits on the control panel main circuit board can be configured by
pressing
2
while viewing Programming Screen #2. The following screens will be displayed:
The Output Circuits can be configured independently by pressing
1
for Output 1,
2
for Output 2,
3
for Output 3 or
4
for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:
Enabled
Pressing
1
while viewing Output Screen #1 will cause the display to change to
Enabled No
. This
will prevent the selected main circuit board NAC from activating its devices. Each press of the
1
key will cause the display to toggle between
Enabled Yes
and
Enabled No
.
Note that if a circuit is disabled, a
trouble
will be logged on the FACP until the circuit is enabled.
The exception is when a Release Circuit is disabled, a
supervisory
will be logged on the FACP until
the circuit is enabled.
Type
Pressing
2
while viewing Output Screen #1 will cause the following screen to be displayed:
Pressing the down arrow key while viewing the Edit Output Type Screen will display additional
screens with the types shown below:
Release Circuit 1
Release Circuit 2
Alarm NAC
Waterflow NAC
Release Stage NAC
Horn NAC
PROGRAMMING
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
OUTPUT CIRCUITS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
NAC Selection Screen
OUTPUT CIRCUITS
1=OUTPUT 4
NAC Selection Screen
OUTPUT #
1=ENABLED YES
2=TYPE ALARM NAC
Output Screen #1
Output Screen #2
OUTPUT #
1=SILENCE NON-SIL
2=AUTO SILENCE NO
3=SIL INHIBIT NO
Output Screen #3
OUTPUT #
1=CODING
STEADY
NAC #
1=ENABLED
2=TYPE ALARM NAC
NAC Screen #1
EDIT OUTPUT # TYPE
1=RELEASE CIRCUIT 1
2=RELEASE CIRCUIT 2
3=ALARM NAC
Edit Output # Type Screen