NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
Programming
Basic Program
ACS Selection Group B:
ACS Selection Group C (SLC #1, Modules 1-64):
Table 2.15 ACS Group B
Point
Type
Red LED
Yellow LED
Switch Function*
1
Input
Zone 57 Active
Zone 57 Trouble
Not Used
2
Input
Zone 58 Active
Zone 58 Trouble
Not Used
3
Input
Zone 59 Active
Zone 59 Trouble
Not Used
to
to (see note 1)
to (see note 1)
43
Input
Zone 99 Active
Zone 99 Trouble
Not Used
44
Output
Zone F1 Active
Zone F1 Trouble
Not Used
45
Output
Zone F2 Active
Zone F2 Trouble
Not Used
to
to (see note 2)
to (see note 2)
52
Output
Zone F9 Active
Zone F9 Trouble
Not Used
53
Release Ckt #0
Zone R0 Active
Zone R0 Trouble
Not Used
54
Release Ckt #1
Zone R1 Active
Zone R1 Trouble
Not Used
to
to
to (see note 2)
to (see note 2)
60
Release Ckt #7
Zone R7 Active
Zone R7 Trouble
Not Used
61
NAC Output
NAC B01 Active
NAC B01 Trouble
Controls NAC B01
62
NAC Output
NAC B02 Active
NAC B02 Trouble
Controls NAC B02
63
NAC Output
NAC B03 Active
NAC B03 Trouble
Controls NAC B03
64
NAC Output
NAC B04 Active
NAC B04 Trouble
Controls NAC B04
* Pressing the switch button when the Switch Function is “Not Used” will cause the associated LED to stop
blinking. This is a local acknowledgement at the annunciator only: no message is sent to the panel.
NOTE:
1. Point number to Zone number relationship is sequential. To determine Point to Zone
relationship, add 56 to Point number to arrive at Zone number.
2. Point number to Zone number relationship is sequential; therefore, point 48 is zone F5 and
point 57 is zone R4.
Table 2.16 ACS Group C
Point
Type
Red LED
Yellow LED
Switch Function
1
Input or Output
Module 001 Active
Module 001 Trouble
Controls Output Module
2
Input or Output
Module 002 Active
Module 002 Trouble
Controls Output Module
3
Input or Output
Module 003 Active
Module 003 Trouble
Controls Output Module
to
to (see note)
to (see note)
64
Input or Output
Module 064 Active
Module 064 Trouble
Controls Output Module
NOTE:
Point number to Module number relationship is sequential; therefore, point 48 is
Module 048.