Basic Program
Programming
Annunciator Options
NOTE:
An ACM-24AT or AEM-24AT LED point must be programmed as a dedicated visual
indicator for a mass notification or CO event. This is not required for displayless systems.
Use Annunciator Selection screens to select information that will display on the ACS annunciators.
(Table 2.13 on page 34 contains the ACS display selections.) Setting
ACS
=
Y
from the “System
Function” screen displays the Annunciator Selection 1 screen, address A1-A11. Press enter to
display Annunciator Selection 2 screen, address A12 - A19:
Enter “N” (ACS Selection Group N) for a TM-4 module used for remote station communication.
Enter “O” (ACS Selection Group O) for a TM-4 used as a municipal box trip. This will provide a
“Master Box” trouble message at the panel.
Refer to page page 41 for further information on Group N and Group O.
ACS Selection Group Example
An example of a screen listing ACS Selection Groups (H, I and M):
Annunciator selections for addresses A1, A2 and A3 (addresses A4-A11 not selected).
• Annunciators set to Address 1 display the status of detectors 1-64 (Group H) on SLC 1
• Annunciators set to Address 2 display the status of detectors 1-64 (Group I) on SLC 2
ACS Address
A1-A11
ACS Selection Group (A-M; 0-9)
or *=not selected
If UDACT=2
: The UDACT is installed with Detector Maintenance Reporting. A24-A31 are
pre-programmed to send control panel status to the UDACT. Only the first 100 detectors on
Loop 1 and Loop 2 participate in Detector Maintenance Reporting. For pre-programmed
point addressing, refer to associated table for Groups P through W on the following pages.
UDACT-2 does not support this option.
If UDACT=1
: The UDACT or UDACT-2 is installed. Addresses A20-A32 are available to
send control panel status to the UDACT (software release #UDACT02.1 or higher) or the
UDACT-2
If UDACT=0
: No UDACT or UDACT-2 is installed. The control panel displays the
Annunciator Selection 3 & 4 screen for addresses A20-A32.
ACS Address
A12-A19
A N N U N S E L E C T I O N 1
A 1 = * A 2 = * A 3 = * A 4 = *
A 5 = * A 6 = * A 7 = * A 8 = * A 9 = * A 1 0 = * A 1 1 = *
A N N U N S E L E C T I O N 2
A 1 2 = * A 1 3 = * A 1 4 = *
A 1 5 = * A 1 6 = * A 1 7 = * A 1 8 = * A 1 9 = * U D A C T = 0
ACS Address (A1)
ACS Selection Group (H)
A N N U N S E L E C T I O N 1
A 1 = H A 2 = I A 3 = * A 4 = *
A 5 = 8 A 6 = * A 7 = * A 8 = * A 9 = * A 1 0 = * A 1 1 = *