NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
27
Basic Program
Programming
2.3.6 Create a Custom Zone Label (5=
ZONE
)
The Zone option lets you change the custom label assigned to zones 1-99.
From the “Basic Program” screen, press the
5
key to display the “Zone
Change” screen as shown below:
The zone number displays in the first line, characters 39 and 40. When changing a zone label,
follow these guidelines.
• For single-digit numbers, enter a leading zero before the digit.
• Enter an alphanumeric zone label into line 2, characters 21–40.
To change a custom label for a zone, follow these instructions:
2.3.7 Program Special Zones (6=
SPL
FUNCT
)
The Special Zone Change option lets you change the program for Special
Zones F0-F9, Releasing Zones R0-R9, FA (Verification), FB (Custom drill
zone) or FC (CO Alarm). From the “Basic Program” screen, press the
6
key to
display the “Special Function Change” screen as shown below:
.
Special Zone Descriptions
Descriptions for each Special Zone that appears in the “Special Function Change” screen are
detailed below:
Table 2.9 Create or Change a Custom Zone Label
To
Do this
Change a zone label
Enter a new zone label from the keypad.
Save the zone label in memory
Press
.
The program stores the zone label in memory and
displays the Zone Change screen with all fields blank.
Leave the Zone Change screen
without changing a zone label
Press .
The display returns to the Program Change screen.
Program Change
Password
C H A N G E Z O N E L A B E L
S E L E C T Z O N E 0 1 - 9 9 :
E N T E R U P T O 2 0 C H A R
blinking cursor prompt
Custom zone label (characters 21-40)
Program Change
Password
S P E C I A L F U N C T I O N : F 0 = P R E S I G R 0 - R 9 = R E L
F 5 - F 6 = T I M E F 7 = H O L F 8 = C O D E
F 9 = P R E - A L A R M
NOTE:
Special Zones F0-F9 appear in the CBE list of a device as ZF0-ZF9. For example, if you
list F0 for a detector, one of the five zones in the CBE list of the detector will display as ZF0.