NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
23
Basic Program
Programming
Modify an Addressable Control Module Point
When you select a point address for modification, the control panel returns a screen that displays
information about the point. For example, the illustration below shows sample information for a
control module (2M101) in the LCD display.
To modify a point, follow these steps. A blinking cursor indicates the selected field.
1. From the programming screen, use the arrow keys to move to a field that you want to modify.
See below for descriptions and settings.
Walk Test Selection: *=off
(default); W=selected
Silenceable: O =selected; *=off (default)
Default zone
Blinking Type Code selection
CBE list
(five zones)
12 spaces for extended
custom label
SLC number (1 or 2)
M (module)
SLC address (001-159)
Switch Inhibit: I=selected; *=off (default)
P R O G R A M C O N T R O L
M O D U L E C O N T R O L 2 M 1 0 1
0 0 _ _ _ _ _ _ _ _ I O W 2 M 1 0 1
20-character user-editable custom label
NOTE:
On a control module, the default zone is always set to Zone 00 (general alarm).
Table 2.5 Modifying Control Module Programming Selections (1 of 2)
Field
Description
Set as follows:
Type Code
Specifies the function of the control
module
Press the
NEXT
or
PREVIOUS
Selection keys to scroll
through valid control module Type Code selections (listed
in Table F.3 on page 115)
Custom Label
20 character custom label.
Change by placing the cursor into the first space of the
field using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any
space necessary between the custom and extended label
fields. An 80-column printout will run the two fields
together.
Extended
Label
12 character custom label extension.
See “Custom Label” above.
CBE list
Up to five software zones can be
entered to define the output responses
of the control module based on
various initiating conditions (events)
Type the number of up to five zones, including E0-E9, F0-
F9, L0-L9, R0-R9, and zones 00-99. The first zone default
is Z00 (general alarm).
Switch Inhibit
Specifies if an operator can manually
activate an output
Type one of the following entries.
I
= Switch Inhibit enabled
*
= no switch inhibit (default for all but releasing circuits)
Silenceable
Specifies if an operator can manually
silence an activated output
Type one of the following entries.
*
= output nonsilenceable
F
= silenceable, resound by fire alarm
U
= silenceable, resound by supervisory alarm
B
= silenceable, resound by security alarm
T
= silenceable, resound by trouble
O
= silenceable, does not resound
If the “Strobe” Type ID is used with System Sensor,
Gentex or Wheelock Strobe synchronization,“*” will
silence the horn portion only, and resound will occur only
by fire alarm. F, U, B, T, or O will silence the entire circuit,
and resound will occur according to the above definitions.