
NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
17
Basic Program
Programming
3. Press the
ENTER
key to add detector 147 to the program with the default program information.
If you want to change the default information, use the programming keys to do so, then press
the
ENTER
key to add detector 147 to the program.
The Autoprogram Summary screen appears. You can verify addition of the detector to the
program by noting the new count of detectors as shown below:
4. Press the
ENTER
key, then press the esc key to save the program in memory and return to the
“Basic Program” screen).
Remove a Device from the Program
You can also use the Autoprogram option to remove addressable detectors and modules from the
control panel program.
The following steps describe how to delete a detector at SLC address 1D133 with 11 detectors
connected to SLC 1 in the existing program:
1. Disconnect and remove the detector from SLC 1 at address 1D133.
2. From the “Basic Program” screen, press the
1
key to start Autoprogram. The Autoprogram
Prompt screen displays while the control panel identifies addressable devices.
3. When finished identifying addressable devices, the control panel displays a screen, indicating a
missing detector at SLC address 1D133 as shown below:
4. Press the
ENTER
key to delete detector 1D133 from the program.
The Autoprogram Summary screen appears. You can verify removal of the detector from the
program by noting the new count of detectors as shown below:
5. Press the
ENTER
key, then press the
ESC
key to save the program in memory and return to the
“Basic Program” screen.
Note that the number of detectors increases (in this example
from 10 to 11) to show the addition of the detector to SLC 1.
L 1 : 0 1 1 D e t s , 1 5 9 M o d s L 2 : 1 5 9 D e t s , 1 5 9 M o d s
S B
B e l l s : 0 4
NOTE:
When using the Autoprogram option with an existing program, the control panel does not
change program information for installed and programmed devices.
Type Code
SLC loop number
D (detector) or M (module)
Three-digit address (001-159)
P R O G R M S M O K E ( I O N ) D E T E C T O R A D D R 1 D 1 3 3
D E V I C E N O T A N S W E R I N G D E L E T E F R M E M ? 1 D 1 3 3
Note that the number of detectors decreases (from 11 to
10) to show the removal of the detector from SLC 1.
L 1 : 0 1 0 D e t s , 1 5 9 M o d s L 2 : 1 5 9 D e t s , 1 5 9 M o d s
S B
B e l l s : 0 4