LDM Series Instruction Manual —
P/N 15885:H3 8/12/2019
33
Configuration for the LDM-32 and System 5000
System 5000 (UL 8th)
B.5 Configuration for the LDM-32 and System 5000
LDM-32 DIP Switch (SW3) settings (for System 5000):
1.
Relay Control:
Future Use - this switch must be set OFF on the System 5000.
None
One
Two
Four
2.
Number of LDM-E32 Expanders Installed
:
OFF
ON
OFF
ON
3.
Number of LDM-E32 Expanders Installed:
OFF
OFF
ON
ON
4.
8-Point Shift
: Set switch ON to shift CPU-5000 LED function annunciation from the first eight annunciator positions on the
LDM-32 to the third LDM-E32 expander positions 57 - 64. This shift can only be set on an LDM-32 set for address 1.
5.
Receive Only
: Set this switch ON for each LDM series that will provide the same information as another LDM series in a different
physical location (when two or more sets of LDM series have the same address, all but one must be configured as Receive Only.)
6.
Piezo Disable
: Set this switch ON to disable the piezo from sounding for any event.
7.
Switch Inhibit: T
o disable the point I/O control switches on the LDMs from functioning, set this switch ON. When inhibited, the
local Lamp Test switch continues to function. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity,
unrecognized by the host System 5000.
8.
Flash Inhibit:
Set this switch ON to disable the flashing of LEDs associated with unacknowledged events. F
lash Inhibit also
disables the piezo from sounding. Flash Inhibit must be ON when using the relay expander module (LDM-R32).
*The lamp driver can be set for addresses 1, 2, 3 or 4. The actual mapping arrangement for a respective module and its expanders
depends on System 5000 annunciator programming. Refer to Document 15584 for details.
12
3
45
6
78
8
8
LDM-32
Switch set to
ON
position
Switch set to
OFF
position
Lamp Driver Address
Set in the range 01-04
Ones
Tens
DIP Switch SW3
(see settings below)
Lamp Driver Mode Switch
SW4
SW4
ALARM/TROUBLE
mode
(SW4 set to right side)
ALARM ONLY
mode
(SW4 set to left side)