
Page 28
IFS-2600
Installation & Programming Manual
P/N 10069 ECN08-0066
OUTPUT RELAY OPTIONS
Optional Relays can be programmed to simulate: -
Isolate Relay
ACF Output
Brigade Relay #1
Brigade Relay #2
Fault Relay
Mains Fail Relay
General Alarm Relay
Bell Output
Door Holder Relay
Door Switch
Reset
Or Can Be Used To:
"MAP AND"
Up to 5 Zones in Alarm
"MAP OR"
Up to 5 Zones in Alarm
“MAP FAULT”
Up to 5 Zones in Fault
“MAP ISOLATE”
Up to 5 Zones in Isolate
“MAP ISO/FAULT”
Up to 5 Zones in Isolate/Fault
DEFAULT SETTINGS
ACF OUTPUT
NON-LATCHING, NORMALLY DE-ENERGISED
ALARM VERIFICATION (AVF)
3 MINUTES
TIME
1/1/11 11:11
ZONE TYPES
STANDARD LATCH 2S
ZONE OUTPUT CONFIG
I-B-G-A-BR1 & BR2
RELAY MAPPING
MAP -OR-, MAPPING = 1 TO 1
IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2.............
The
2600
PANEL is self-configuring on power-up therefore it is not necessary to program the number
of relay boards.
Zone expansion boards fitted must have the correct jumper selected.