background image

FMM-4-20 
4-20mA Analog Input Module

BeFore InstAllIng

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual for detailed system information. If the 
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

generAl DescrIptIon

The FMM-4-20 4-20mA Analog Input Module is intended for use in intelligent, 
two-wire  systems,  where  the  individual  address  of  each  module  is  selected 
using  the  built-in  rotary  switches.  This  module  allows  intelligent  panels  to 
interface and monitor two-wire or three-wire sensors, that produce a 4-20mA 
signal output. It transmits the status (normal, open, or alarm) of one sensor 
back to the control panel. The FMM-4-20 has a panel controlled LED indicator. 
Only one sensor can be connected to the FMM-4-20.

coMpAtIBIlIty requIreMents

To ensure proper operation, this module shall be connected to a compatible 
Notifier system control panel only (list available from Notifier). In addition, 
please refer to Notifier Device Compatibility document number 15378 for the 
list of compatible devices.

FIgure 1. controls AnD InDIcAtors:

C0218-05

specIFIcAtIons

SLC

  Normal Operating Voltage: 

15 to 32 VDC

  Maximum Current Draw: 

9.3 mA (LED on)

  Average Operating Current: 

1 mA (LED flashing)

External Supply

  Normal Operating Voltage: 

24 VDC Nominal

  Standby Current: 

10 mA

  Maximum Current: 

510 mA

Initiating Device

  Maximum Current: 

500 mA

Temperature Range: 

–10°C to 60°C

Humidity: 

10% to 95% Non-condensing

Dimensions: 

4

1

/

2

˝ H × 4˝ W × 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box

NO-460-003 

I56-2991-002

I56-299

1-00

2

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161

InstAllAtIon AnD MAIntenAnce InstructIons

MountIng

The FMM-4-20 mounts directly to 4-inch square electrical boxes (see Figure 
2).  The  box  must  have  a  minimum  depth  of  2

1

/

8

  inches.  Surface  mounted 

electrical boxes (SMB500) are available from Notifier.

FIgure 2. MoDule MountIng:

C0449-01

WIrIng

NOTE:  All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and 
regulations. This module is intended for powerlimited wiring only.

1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.  Set the address on the module per job drawings.
3.  Secure module to electrical box (supplied by installer), Figure 2.

Reviews: