Notifier FirstCommand Series Manual —
P/N LS10001-001NF-E:H 1/8/2018
67
Programmed Activation by FACP
Programming
Example 3:
If two devices are being programmed and the
first
addressable input device is programmed to Zone 7 and Zone 35, and a
second
addressable input device is programmed to Zone 5 and Zone 35, activation of the first addressable input device (address 12 in the
example below) will cause Message 2 to be generated over speaker circuit 3. If the second addressable device (address 20 in the example
below) is also activated, Message 1 will now be transmitted over speaker circuit 3 since Message 1 has a higher priority then Message 2.
FACP Programming Menus
To Program one of fourteen messages to a speaker zone, press the
ENTER
key at the FACP. The following screen will be displayed:
Access Programming Mode by pressing the
2
key. The following screen will be displayed:
Entering the
Master
level password (default
00000
) will cause the following screen to appear:
Select the
Zone Setup
option by pressing
3
. The following screens will be displayed.
Pressing
3
while viewing Zone Setup Screen #3 will cause the following screen to be displayed:
Zone 5 and Zone 35
Zone 7 and Zone 35
Addressable Pull Station
(address 12)
Message 1
(highest priority of the three )
programmed to
activate
Speaker Circuit 3
Addressable Pull Station
(address 20)
programmed to
Message 2
(2nd highest priority of the three)
activate
e
c
c
e
x
3
.w
m
f
1=READ STATUS
2=PROGRAMMING
3=
4=
PROGRAMMING
ENTER PASSWORD
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
ZONE MESSAGE
1=Z00 NO MESSAGE
2=Z01 NO MESSAGE
3=Z02 NO MESSAGE
Summary of Contents for Notifier FirstCommand Series