Section 3: Programming
All NFC programming is done using the built-in web-based programming utility. It is recommended that tone selection, message repeat
cycles and background music options be reviewed and approved by the local AHJ.
To start programming, use a standard CAT5e Ethernet (patch) cable to connect a personal computer’s IP port (Ethernet) to the IP port
(Ethernet) J2 on the main control board (right side of the board). Set the computer’s local area network connection address as follows:
IP address: 169.254.3.5
Subnet mask: 255.255.0.0
Activate the PC’s web browser (Google Chrome or Mozilla Firefox). Enter the following in the browser’s navigation bar:
http://169.254.3.3
The main menu will display and allow further menu navigation.
Security and Data Protection:
NO ENCRYPTION EMPLOYED
•
Communication Security:
– a. Level 1
•
Stored Data Security:
– a. Level 0
•
Access Control Security:
– a. Level 1
•
Physical Security:
– a. Level 1
Audit Control: not provided
3.1 NFC-50/100 Panel Installation/Maintenance Security Checklist
System Description:_____________________________________________________
System Location: _______________________________________________________
Installer: _______________________________________ Date: __________________
Complete the following security tasks for each NFC-50/100 installation.
Install the NFC-50/100 panel in a secure location considering both software and hardware vulnerabilities.
Change the default password to a unique password.
Securely configure networks and firewalls.
Assess security risks.
Develop a Disaster and Recovery Plan.
Develop a Backup and Recovery Strategy.
Install, configure, and maintain anti-virus software on all computers which access the panel.
Keep the operating system updated and maintain version compatibility with the panel.
Deliver all required system information upon delivery to the system owner.
Train end-users on security maintenance tasks upon system delivery.
For decommissioning, dispose of data securely.
Ensure the Ethernet cable is removed from the NFC-50/100 when not being utilized for configuration.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, and in the standard for Communication and Control Units for Mass Notification Systems, UL
2572, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature or
option
Permitted in
UL 864/UL 2572? (Y/N)
Possible settings
Settings permitted in
UL 864/UL 2572
AC Loss Delay
Y
AC Loss Delay = 0, 2 (factory default), 6, 12, or 23 hours
Refer to “AC Loss Delay” on page 53.
AC Loss Delay = 2 hours
24 Hour Resound
Y
24 Hour Resound = Enabled
24 Hour Resound = Disabled
Refer to “24 Hour Resound” on page 53
24 Hour Resound Enabled
Active With Page
N
Enable/Disable
Disabled
Page Timeout
N
0-60 in 15 second increments
0 seconds
NOTE:
Be sure to record the computer’s original addresses so they can be restored when NFC programming is complete.
NOTE:
All screen shots reflect default programming.
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...