 DOC-02-159:rev C - Page 1 of 8  

AFP-3030

Intelligent Fire Alarm Control Panel

Intelligent Fire Systems

GENERAL

The AFP-3030 is an intelligent Fire Alarm Control Panel (FACP) 
with a flexible and scaleable architecture which makes it suitable 
for virtually any application including large scale networked 
facilities. Fire emergency detection and evacuation are extremely 
critical to life safety, and the AFP-3030 is ideally suited for these 
applications.

The AFP-3030 is part of the ONYX® Series of products from 
NOTIFIER. With one to ten Signaling Line Circuits (SLCs), the 
AFP-3030 supports up to 3,180 intelligent addressable devices 
per panel and is networkable up to 200 nodes. 

A host of other options are available, including single- 
or multichannel voice; LED, LCD, or PC-based graphic 
annunciators; networking; advanced detection products for 
challenging environments, and many additional options.

Connectivity  with  a  range  of  NOTI•FIRE•NET™  integration 

options such as Bacnet, Modbus, OnyxWorks and 
Notifier WebServer (NWS-3) permit the AFP-3030 and 

NOTI•FIRE•NET™ to integrate into critical component building 

management systems. 

FEATURES

• 

One to ten isolated intelligent Signaling Line Circuits

• 

Up to 159 detectors and 159 modules per SLC, 318 
devices per loop / 3,180 per FACP (or network node) 

• 

Detectors can be any mix of ionization, photo, laser 
photo, thermal, or multi-criteria detectors; modules 
can be addressable manual call points, normally open 
contact devices, two-wire smoke detectors, notification, 
relay or 4-20 mA modules

• 

Large 640-character LCD backlit displayor display-less 
(a node on a network)

• 

Network up to 200 nodes with high-speed Noti-Fire-Net

• 

VeriFire Tools non-proprietary online/offline program, test 
and reporting PC software.

• 

Weekly Occupancy Schedules allow changing sensitivity 
by time of day and day of week

• 

With built-in SLC Local mode operation; the system is 
capable of activating sounders and relays if a fire alarm 
condition is present even if the central processing unit 
(CPU) fails

• 

Range of annunciators for ancillary display & control

• 

History file with 4000-event capacity plus separate 
1000-event alarm-only file

• 

Advanced history filters allow sorting by event, time, 
date, or address

• 

Alarm Verification Facility (AVF) selection per point, with 
automatic counter

• 

Auto-programming and Walk Test reports

• 

Alarm delay operation

• 

Field-programmable on panel with QWERTY keypad

• 

Non-alarm points for lower priority functions

• 

Remote Silence, System Reset, Evacuate via monitor 
modules

• 

Support for AS1668.1 compliant smoke control with 
SCS Series smoke control system

AFP-3030 in CAB-900 and CAB650

Summary of Contents for Notifier AFP-3030

Page 1: ...ctors and 159 modules per SLC 318 devices per loop 3 180 per FACP or network node Detectors can be any mix of ionization photo laser photo thermal or multi criteria detectors modules can be addressable manual call points normally open contact devices two wire smoke detectors notification relay or 4 20 mA modules Large 640 character LCD backlit displayor display less a node on a network Network up ...

Page 2: ...Advanced ONYX intelligent sensing including automatic drift compensation to reduce unwanted alarms and provide warning of contamination build up Addressable operation pinpoints the fire location Protection against the entry of insects and other contaminants FAPT 851AUS Acclimate Plus Intelligent Multi Criteria Detector Detector automatically adjusts sensitivity levels without operator intervention...

Page 3: ... of ONYX Intelligent Sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre alarm decisions Without statistical sacrifice in the ability to resist false alarms it allows a sensor to increase its sensitivityto actual smoke by a factor of almost two to one Alarm Verfication Facility AVF All devices are capable of performing an alarm verification faci...

Page 4: ...s assembly See DOC 02 130 DA 30 DA 60 DA 120 Digital Amplifier DA 30 is 30 watts DA 60 is 60 watts DA 120 is 120 watts 100 Vrms Includes audio input and amplified output supervision See DOC 02 066 DA DISP A DA DISP B DA DISP C DA DISP D DA DISP E Display control and paging microphone modules for DA series amplifiers See DOC 02 066 SDM 4 4 way Speaker distribution module for use with DA series ampl...

Page 5: ...ntrol module See DOC 02 044 XP6 MA FlashScan six zone interface module connects intelligent alarm system to two wire conventional detection zone See DOC 02 043 XP6 R FlashScan six relay Form C control module See DOC 02 045 XP10 M FlashScan ten input monitor module See DOC 02 046 IMX IE Translator module for use with intrinsically safe devices See DOC 02 129 Y 2221 Single channel galvanic isolator ...

Page 6: ...able Modules NFX MCP FRM 1 XP6 C etc ARE Interface Interface to Alarm Routing Equipment ACM 8RA Relay Expansion Module ACM 24AT ACM 48A ACS Annunciators Module SCS 8A Smoke Control Station DA 30 60 120 DA Series Occupant Warning System Intelligent Detectors FAPT 851AUS FSP 851AUS FSL 751 etc LDM 32 Custom LED mimic LCD2 80 LCD Remote Display AFP 3030 Connection Overview ...

Page 7: ... A 0 150 A LCM 320 0 130 A LEM 320 0 100 A NOTE See AFP 3030 Manual DOC 01 031 for a complete current draw calculation sheet and details of input and output values Enclosure Specifications CAB650 650mm h x 450mm w x 190mm d CAB900 900mm h x 450mm w x 190mm d CAB650 BB 250mm h x 450mm w x 190mm d 18U 887mm h x 610mm w x 285mm d 28U 1330mm h x 610mm w x 375mm d 40U 1865mm h x 610mm w x 375mm d 18U B...

Page 8: ...ithout notice 2015 Honeywell International Inc All rights reserved Unauthorized use of this document is strictly prohibited ISO9001 FS 520324 ENGINEERING MANUFACTURING QUALITY SYSTEMS For more information please contact your nearest Notifier Office or Distributor www notifier com au www notifier co nz IntelliQuad and NOTI FIRE NET are all trademarks and Acclimate Plus FlashScan NOTIFIER ONYX and V...

Page 9: ...Communications and Communications Fail LED indication Lamp test button 16 touch pad switches Switches may be set in banks of 8 to either toggle on toggle off or momentary modes 16 red and 16 yellow LED s ACM 32A This module may be programmed to show the status of any point zone or module on the system Features Communications and Communications Fail LED indication Lamp test button 32 red LED s Inte...

Page 10: ...a site specific mimic panel or wherever LED annunciation is required Features 32 alarm lamp driver transistors sink to power common on alarm May be powered by 24 VDC from the panel or by remote power supplies Efficient switch power converter reduces power consumption Microprocessor controlled electronics fully supervised Plug in terminal blocks for ease of installation and service LDM R32 Notifier...

Page 11: ... signal for a removed or improperly installed sensor cover The Notifier InnovairFlex housing provides a 20 mm conduit knockout and ample space to facilitate easy wiring and mounting of a relay module FEATURES Photoelectric integrated low flow technology Air velocity rating from 0 5 m s to 20 32 m s Versatile mounting options square or rectangular configuration Replaceable plug in sensor heads Broa...

Page 12: ...s photoelectric smoke detector sold seperately FSP 851AUS FlashScan low profile photoelectric smoke detector SDX 851AUS CLIP low profile photoelectric smoke detector DST1 Metal sampling tube to suit duct widths up to 0 3m DST3 Metal sampling tube to suit duct widths 0 6m 1 2m DST5 Metal sampling tube to suit duct widths 1 2m 2 4m DST10 Metal sampling tube to suit duct widths 2 4m 3 7m ETX Metal ex...

Page 13: ... audible visual power or high level audio speakers Operation Each FCM 1 uses one of 159 possible module addresses on a SLC loop 99 on CLIP loops It responds to regular polls from the control panel and reports its type and status including the open normal short status of its Notification Appliance Circuit NAC The LED blinks with each poll received On command it activates its internal relay The FCM ...

Page 14: ...ributor www notifier com au Specifications Normal Operating Voltage 15 to 32 VDC Maximum Current Draw 6 5 mA LED on Average Operating Current 350 μA direct poll 375 μA group poll with LED flashing 485 μA Max LED flashing NAC shorted Maximum NAC Line Loss 4 VDC External supply voltage Maximum NAC Regulated 24VDC between Terminals T10 and T11 Maximum Speakers 125 V RMS 50W Drain on external supply 1...

Page 15: ...ogy for fast response Rate of rise model FDX 851R 8 3 C per minute Factory preset at 63 C fixed temperature rating Compatible with CLIP protocol systems Direct dial entry of address 01 99 mode loops Visible LEDs blink every time the unit is addressed 360 field viewing angle of the visual alarm indicators LEDs blink in Normal condition and turn on steady in Alarm Integral communications and built i...

Page 16: ...t Notifier Sales Office or Distributor www notifier com au Specifications Sensitivity Fixed 63 C Sensitivity Rate of Rise 63 C or an increase of greater than 8 3 C min Operating Voltage Range 15 VDC to 32 VDC Standby Current 300 μA 24 VDC one communication every 5 seconds with LED blink enabled Maximum Alarm Current LED On 6 5 mA 24 VDC Operating Humidity Range 10 to 93 Relative humidity Non conde...

Page 17: ...blink may be deselected globally affects all devices High noise immunity EMF RFI Wide viewing angle of LED Direct dial entry of address 01 159 for FlashScan loops 01 99 for CLIP mode loops Compatible with FlashScan and CLIP protocol systems Applications The FRM 1 may be programmed to operate dry contacts for applications such as door holders and Air Handling Unit shutdown Operation Each FRM 1 uses...

Page 18: ...operating voltage 15 to 32 VDC Maximum current draw 6 5 mA LED on Average operating current 230 μA direct poll 255 μA group poll EOL Value Not used Temperature range 0 C to 49 C Humidity range 10 to 93 non condensing Current Ratings 3 0 A 30 VDC resistive non coded 2 0 A 30 VDC resistive coded 0 9 A 110 VDC resistive non coded 0 9 A 125 VDC resistive non coded 0 5 A 30 VDC inductive L R 5 ms coded...

Page 19: ...s warehouses sporting arenas concert halls and enclosed parking facilities Installation of the single ended reflective design is much quicker than a dual ended projected beam detector Alignment is easily accomplished with an optical sight and a two digit signal strength meter incorporated into the beam detector Listed for operation from 30 C to 55 C the FSB 200 and FSB 200S are usable in open area...

Page 20: ...S451 RTS451KEY Indicators Alarm Remote Output Local LED red Trouble Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green with communication Alignment Aids Optical Gunsight coarse adjustment 00 to 99 Digital Display fine adjustment Relays Alarm Trouble Sensitivity Digital Display Read out in Percent Obscuration Environmental Temperature 30 C to 55 C...

Page 21: ...elligent devices communicate in a grouped fashion If one of the devices in the group has new information the panel s CPU stops the group poll and concentrates on single points The net effect is response speed greater than five times that of earlier designs Features Sleek low profile design Addressable analog communication Stable communication technique with noise immunity Low standby current Two w...

Page 22: ...cations are subject to change without notice For more information contact your nearest Notifier Sales Office or Distributor www notifier com au Specifications Size 5 3cm high x 10 4cm diameter installed in B501 base Operating Temperature FSP 851 0 C to 49 Relative Humidity 10 93 noncondensing Electrical Specifications Voltage Range 15 32 volts DC peak Standby Current max avg 300μA 24VDC one commun...

Reviews: