40
ACPS-610/E Manual —
P/N 53018:A1 07/31/2007
Applications
Style B (Class B) Initiating Device Circuit
4.3 Style B (Class B) Initiating Device Circuit
Figure 4.3 Style B (Class B) IDC
4.4 Synchronization
The ACPS-610 provides synchronization to Gentex, System Sensor SpectrAlert and SpectrAlert
Advance Series, and Wheelock strobes and horns. When the ACPS-610 is set for synchronization,
these NAC devices will flash and/or sound together.
The ACPS-610 can also provide synchronization for bells and horns when used with a UZC-256
Universal Zone Coder if the NAC output is configured for coded signals only.
End-of-Line
Resistor 47K
ohm
UL listed power supervision relay
(shown in energized state)
Four-wire
smoke detector
Four-wire
smoke detector
Resettable 24
VDC power
FMM-1
SLC to next
device
SLC from
last device
ACPS-610
acp
s
-6
10
_sm
o
kd
eta
p
p
.cdr
NOTE:
Do not place strobes from any manufacturer onto a coded output.
For example SpectrAlert and SpectrAlert Advance Series horns and strobes can not be
synchronized with a UZC-256 or any coded output.