NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
55
Point Program
Program
Pressing the
MORE
soft key on this Module Point Programming screen will display this screen:
Figure 3.44 Module Point Programming Screen 3 (Monitor)
W A T E R F L O W D E L A Y :
When the
WATERFLOW DELAY
option is set to
0
, waterflow events are
immediately reported to the panel upon activation. If a non-zero value is entered in the
WATERFLOW
DELAY
, activation of a waterflow event is delayed for the duration of that time. The waterflow event will
have to remain active for the duration of the delay. If the waterflow event does not remain active for the entire
delay duration, the waterflow event will not be reported to the panel.
Default:
0
Range:
0 - 6 0
seconds
A C C E P T :
Press to save screen entries.
Module Point Programming (Control Module)
Pressing the
MORE
soft key at the Module Point Programming screen will display this screen if the
module type was control.
Figure 3.45 Module Point Programming Screen 2 (Control)
M O D U L E P O I N T P R O G R A M M I N G
L 0 3 M 1 5 0
W A T E R F L O W D E L A Y : 3 0
A C C E P T
B A C K
M O D U L E P O I N T P R O G R A M M I N G
L 0 3 M 1 5 0
L O C A L M O D E : O N
Z O N E M A P :
Z 0 0 0 , Z 1 0 4 , Z 1 0 5 , Z 1 0 6 , Z 1 0 7
Z 1 1 0 , Z 1 1 4 , Z 1 1 5 , Z 1 1 6 , Z 1 1 7
W A L K T E S T : O F F
S W I T C H I N H I B I T : Y E S A C C E P T
S I L E N C E A B L E : N O B A C K
Zone Map Position 1 - Use for group zone
disable participation.