NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
Program
Point Program
Pressing the
THRESHOLD
SETUP
soft key at the Module Point Programming screen will display
this screen.
Figure 3.43 FMM-4-20 Threshold Setup Screen
Soft Keys
T H R E S H O L D
N U M B E R :
Enter the threshold number (1 - 5) that will be described in this screen.
T H R E S H O L D
V A L U E :
Enter the value for this threshold. (Threshold value is represented in the unit
type specified on the FMM-4-20 Device Setup Screen)
E V E N T :
Select the event type that will generate when this threshold is reached. Selections are
NO
EVENT
,
TROUBLE
,
FIRE
,
SUPERVISORY
,
SECURITY
,
NONFIRE
,
CRITICAL
PROCESS
.
T R O U B L E
T Y P E :
Select a trouble type for this threshold:
TROUBLE
1
,
TROUBLE
2
or
DEVICE
INHIBIT
. Device Inhibit will generate a trouble when the FMM-4-20 is in a self-calibration state.
E V E N T
T R I G G E R :
Select
LOWER
LEVEL
(values are falling),
UPPER
LEVEL
(levels are rising), or
SAME
LEVEL
.
T R A C K I N G / L A T C H I N G :
Select
TRACKING
or
LATCHING
for the threshold trouble. If more than
one threshold has been programmed as latching, the first threshold reached will be the one that is latched.
A C C E P T :
Press to save screen entries.
M O D U L E P O I N T P R O G R A M M I N G
L 0 3 M 1 5 0
T H R E S H O L D N U M B E R 1
T H R E S H O L D V A L U E : 5 0 0 . 2 5 P P M
E V E N T T R O U B L E L A T C H I N G
T R O U B L E T Y P E : T R O U B L E 1 A C C E P T
E V E N T T R I G G E R : L O W E R L E V E L B A C K