NFS2-3030 Programming Manual —
P/N 52545:K1 03/20/2012
49
Point Program
Program
ALARM SENSITIVITY TABLE:
This table will toggle from
ALARM
to
PREALARM
based on
which sensitivity value is being entered. The table will display the values for this type of detector.
Detector Occupancy Schedule
Figure 3.37 Detector Occupancy Schedule Screen
Soft Keys
WEEKLY OCCUPANCY SCHEDULE:
Press this soft key to place the cursor at the underlined
field. There can be up to ten Weekly Occupancy Schedules. Enter a value of zero through ten. Zero
indicates no schedule is applied, and occupied detector sensitivity values are used.
ACCEPT:
Press this key to accept the change made and return to the previous screen.
Detector Point Programming (3)
Press the
MORE
soft key on the Detector Point Programming (2) screen to display this screen.
Figure 3.38 More Detector Point Programming (3) Screen
Soft Keys
LOW TEMP ENABLE:
Press this softkey to select
YES
or
NO
to enable the Low Temperature
Warning for the PHOTO/CO detector. This field is only available when programming a
PHOTO/CO smoke detector.
D E T E C T O R O C C U P A N C Y S C H E D U L E
W E E K L Y O C C U P A N C Y S C H E D U L E : 1 0
S U N D A Y - -
M O N D A Y 0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
T U E S D A Y 0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
W E D N E S D A Y 0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
T H U R S D A Y 0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
F R I D A Y 0 8 : 0 0 - 1 2 : 0 0 , 1 3 : 0 0 - 1 8 : 0 0
S A T U R D A Y 0 8 : 0 0 - 1 2 : 0 0 , -
H O L I D A Y U N O C C U P I E D
A C C E P T
B A C K
D E T E C T O R P O I N T P R O G R A M M I N G
L 0 3 D 1 2 3
L O W T E M P E N A B L E : Y E S
P R E A L A R M : A L E R T C O P R E - A L A R M : Y E S
S I L E N C E A B L E : N O
I N T E L L I G E N T S O U N D E R : Y E S A C C E P T
S O U N D E R B A S E S E T U P B A C K