NetAXS™ NX4L1 Access Control Unit Installation Guide

Document 7-901099V3

 

67

A

NetAXS™ Standalone Operation

1.0  Basic Standalone Operations

1.1  Card Read / Door Lock Operation

1. Present a card to a reader.

2. The reader sends the card number to a reader input on the panel.

3. The panel searches its database and:

If it is a valid card, then energize the door relay associated with the particular 
reader input. The card is valid when it is in the card database on the panel and 
the current time and date conforms to the time zone associated with the card.

If it is not a valid card, the door relay remains locked.

1.2  Door Egress / Door Lock / Door Status Operation

1. Activate the door egress input.

2. The panel energizes the door relay associated with the particular door egress input 

for a default time of 10 seconds.

3. If the door status goes from close to open to close again during the 10 second door 

open period, the door relay will be immediately de-energized.

Summary of Contents for NETAXS NX4L1

Page 1: ...July 2016 2016 Honeywell All rights reserved 7 901099V3 Honeywell NetAXS NX4L1 Access Control Unit Installation Guide ...

Page 2: ...ited States of America Honeywell reserves the right to change any information in this document at any time without prior notice Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellaccess com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywellaccess com to...

Page 3: ... 16 2 2 NetAXS Access Overview 16 3 0 Panel Components and Descriptions 17 3 1 NetAXS Access Control Unit 18 3 2 Power Supply 19 3 3 Batteries 19 3 4 Enclosure 19 3 5 Suppressors 19 4 0 Installation 20 4 1 Installing the Optional AC Inlet 21 4 2 Typing the Field Wiring in the NX4L1 Cabinet 22 4 3 Cabinet Mounting 23 4 4 Reader Wiring 27 4 5 Supervised Input Wiring 28 4 6 NX4L1 Control Output Wirin...

Page 4: ... Converter to RS 485 Connection via PCI 2 54 5 13 Fiber Converter to RS 485 Connection via NetAXS 55 5 14 N 485 PCI 2 NetAXS Access Controller Panel Connection Detail 56 5 15 NetAXS NetAXS Access Controller Panel Connection Detail 57 6 0 NetAXS Startup 58 6 1 LED Operation 58 7 0 Hardware Specifications 60 7 1 Relay Contacts 60 7 2 Reader Interface 60 7 3 Maximum Output Loading 60 7 4 Common Conne...

Page 5: ...d 69 3 2 D Date Command 70 3 3 L Time Zone Command 71 3 4 C Card Add Command 72 3 5 C Card Delete Command 72 3 6 W Input Command 73 3 7 P Interlock Command 73 3 8 Flow Control Disable Enable Command 74 4 0 NetAXS Panel Defaults 75 4 1 Reader Ports 75 4 2 Reader LED Outputs 75 4 3 Reader Tamper Inputs 76 4 4 Door Egress Inputs 76 4 5 Door Status Inputs 77 4 6 ACFAIL and Panel Tamper Inputs 77 4 7 A...

Page 6: ...6 www honeywell com ...

Page 7: ... Default Downstream I O Configuration with Wiring 41 Figure 18 RS 485 Connection via PCI 2 42 Figure 19 RS 485 Connection via NetAXS 43 Figure 20 RS 485 Connection via NetAXS with Multidrop Panels at Both Ends 44 Figure 21 RS 485 Connection via PCI 2 with Multidrop Panels at Both Ends 45 Figure 22 RS 232 Connection 46 Figure 23 Ethernet Connection 47 Figure 24 LANSRLU1 Connection 48 Figure 25 RS 4...

Page 8: ...8 www honeywell com Figure B 1 Twisted Pair 79 Figure B 2 RS 485 Wiring for NetAXS 4 Loop 81 Figure B 3 RS 485 Wiring for a Mixed Loop 82 ...

Page 9: ...lectrical Entries 27 Table 2 Reader Wiring 27 Table 3 Default Supervised Input Assignments 28 Table 5 DIP Switch Settings 38 Table 6 NX4IN DIP Switch and Jumper Settings 39 Table 7 LED Status 59 Table 8 Communications and Wiring 61 Table 9 Reader Wiring 62 Table 10 Troubleshooting Problems and Solutions 65 ...

Page 10: ...10 www honeywell com ...

Page 11: ...g WIN PAK or related products for use as a primary warning or monitoring system Primary warning or monitoring systems should always meet local fire and safety code requirements The installer must also test the system on a regular basis by instructing the end user in appropriate daily testing procedures Failure to test a system regularly could make installer liable for damages to the end user if a ...

Page 12: ...connection with the acts or omissions of the Customer and its agents and employees and from and against all claims demands losses and liability for costs of fees including reasonable attorneys fees in connection therewith 1 3 Limited Warranty All Products sold or licensed by Honeywell Access Systems HAS include a warranty registration card which must be completed and returned to HAS by or on behal...

Page 13: ...erence to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Re orient or re locate the receivin...

Page 14: ...alone system the computer terminal NetAXS gateway panel and N 485_PCI 2 adapter appear in these sections only to illustrate the installation and programming of the NetAXS panel UL has not evaluated the compatibility of downstream I O devices see Section 4 10 Downstream I O on page 39 with the NetAXS panel All wiring methods shall be performed in accordance with NFPA70 local codes and authorities h...

Page 15: ...Control Unit Installation Guide Document 7 901099V3 15 The model NX4L1 control units are compatible with the following Listed reader heads Honeywell OmniAssure OT30 Honeywell OmniClass OM40 Honeywell OmniClass OM55 Honeywell OmniProx OP30 Honeywell OmniProx OP40 ...

Page 16: ... over a standard network protocol Access control units readers door strikes and video and other devices for example are configured to control and monitor the access to a company site 2 2 NetAXS Access Overview A NetAXS access control system consists of a host system and NetAXS access control units that meet existing N 1000 III IV specifications and that communicate with each other and with a varie...

Page 17: ...nts are enclosed in a pre wired cabinet The power supply provides power for the panel control board which is a four reader panel providing access control for up to four doors The following figure shows the NX4L1 panel components Figure 1 NX4L1 Panel Components Enclosure Tamper Switch Cables with heat shrink barriers Cables with heat shrink barriers Pb Pb 4 A 250 V Bussmann S500 type or Littelfuse ...

Page 18: ...atus on each door Supervised inputs for Tamper External Power Fail and four Reader Tampers are supplied as well and they can be used as additional inputs when not required for their default purpose CAUTION The NetAXS board must not be used to power locks All locks must be powered through the relay board Real Time Clock Protection The panel RTC is backed up using a super capacitor The super capacit...

Page 19: ...pen or remove the power supply cover 3 3 Batteries For the NX4L1 two 12 VDC 7 Ah sealed lead acid batteries Honeywell order number 3 000066 wired in series must be used to have backup battery capability The batteries will provide standby backup power depending upon system configuration and activity The batteries are wired in series positive on one battery to negative on the other and connected to ...

Page 20: ...he Power Connection option see Installing the Optional AC Inlet on page 21 for instructions The power inlet terminal block can accommodate wire sizes up to 12 AWG Wiring to a 20 amp branch circuit requires 12 AWG insulated copper wire Wiring to a 15 amp branch circuit requires 14 AWG insulated copper wire Connect the line neutral and earth ground wires to the appropriate terminal on the power inle...

Page 21: ...attery cable to the remaining positive red battery terminal 14 Attach the negative black power supply to battery cable to the remaining negative black battery terminal 15 For panels using the Ethernet connection the cable clamp HAS part number 3 000342 must be used for the panel to pass the FCC Part 15 Class B requirements Snap the clamp around any portion of the Ethernet cable that is inside of t...

Page 22: ... and symbols represent wire tie points Wiring shown as represent shrink wrap barrier protection 0 028 inch thickness minimum where spacing between non power limited and power limited wiring is less than 0 25 inches Location of wire tie points and suggested routing of Class 2 power limited field wiring to maintain a minimum of 0 25 inch spacing from non power limited wiring ...

Page 23: ...nsions and knockout placement that you will need to mount the cabinet See Table 1 on page 27 for dimensions of the conduit entries into the cabinet Figure 3 NetAXS Panel Cabinet Back View 0 0 3 13 32 86 51 mm 9 3 8 238 50 mm 22 29 32 581 6 mm 27 32 21 8 mm 8 27 32 225 mm 15 5 32 385 mm 16 27 32 428 2 mm 17 23 32 450 mm 2 9 16 65 mm 23 32 18 mm 15 32 11 51 mm 15 32 11 51 mm 0 23 1 8 587 mm 23 29 32...

Page 24: ...Panel Cabinet Top View Figure 5 NetAXS Panel Cabinet Bottom View 0 1 31 32 50 mm 4 1 8 105 mm 1 5 8 41 mm 31 32 25 mm 0 13 19 32 345 mm 15 3 4 400 mm Back 0 0 31 32 25 mm 1 5 8 41 mm 1 31 32 50 mm 4 1 8 105 mm 5 23 32 145 mm 8 27 32 225 mm 15 3 4 400mm 13 19 32 345 mm 12 305 mm Back ...

Page 25: ...ol Unit Installation Guide Document 7 901099V3 25 Figure 6 NetAXS Panel Cabinet Left View 0 1 5 8 41 mm 2 5 32 55 mm 0 2 9 16 65 mm 4 23 32 120 mm 4 17 32 115 mm 6 11 16 170 mm 8 21 32 220 mm 10 10 16 270 mm 16 30 32 430 mm 18 29 32 480 mm 22 3 8 568 5 mm 31 32 25 mm Back ...

Page 26: ... 3 11 16 93 5 mm 1 5 8 41 mm 0 0 0 0 2 9 16 65 mm 4 23 32 120 mm 6 11 16 170 mm 8 21 32 220 mm 10 10 16 270 mm 15 3 4 400 mm 17 23 32 450 mm 22 3 8 568mm 20 11 32 517 mm 17 3 16 436 87 mm 20 1 8 511 5 mm 20 15 16 532 mm 2 19 32 65 mm 1 31 32 50 mm 31 32 25 mm 1 19 32 40 1 mm 1 3 16 30 5 mm 13 16 21 mm Back ...

Page 27: ...le shield should be grounded at the panel only Grounding at both ends can cause ground loops which can be disruptive The maximum recommended length of wiring is 500 feet per reader Note Incorrect wiring of the reader to the panel can cause the panel to stop operating Table 1 Cabinet Electrical Entries ENCLOSURE CONDUIT 1 2 12 7 mm CONDUIT 3 4 19 0 mm CONDUIT 1 25 4 mm CONDUIT 2 50 8 mm Top 5 5 N A...

Page 28: ...tion for each terminal position The following figure shows the typical wiring for a supervised input Figure 8 Typical Supervised Input Wiring Diagram Table 3 Default Supervised Input Assignments Terminal Position Default Function TB4 1 Door 1 REX Egress TB4 3 Door 1 Status TB4 4 Door 2 REX Egress TB4 6 Door 2 Status TB8 1 External Power Supply AC FAIL TB8 3 Panel Tamper TB13 1 Door 3 REX Egress TB...

Page 29: ...relay Relay 1 is defaulted for control of the Door 1 lock Relay 2 is defaulted for the control of the Door 2 lock Relay 3 is defaulted for the control of the Door 3 lock and Relay 4 is defaulted for the control of the Door 4 lock Relays 5 8 are used as auxiliary relays Refer to the NetAXS Access Control Unit User s Guide for details on controlling the relay operations The NX4L1 is wired to enable ...

Page 30: ...the FACP input move the DIP switch to the ON position The Power Distribution Output board has a green LED that indicates the status of the external FACP input The LED will turn on when the input is active and turn off when inactive The Power Distribution Output board has two dry contact outputs FACP fire and power fail that can be used to monitor the general condition of the system The TRBL relay ...

Page 31: ... CLOSE TO THE FIELD LOAD FIELD WIRING FROM EXTERNAL FIRE ALARM CONTROL PANEL DOOR LOCK STRIKE OR OTHER FIELD DEVICE POWER DISTRIBUTION BOARD 1 NC 1 COM 1 NO 2 NC 2 COM 2 NO 3 NC 3 COM 3 NO 4 NC 4 COM 4 NO 8 NO 8 COM 8 NC 7 NO 7 COM 7 NC 6 NO 6 COM 6 NC 5 NO 5 COM 5 NC IN 1 IN GND IN 2 IN GND IN 3 IN GND IN 4 IN GND IN 5 IN GND IN 6 IN GND IN 7 IN GND IN 8 IN GND OUT 1 NC OUT 1 COM OUT 1 NO NEG 1 O...

Page 32: ...e NetAXS panel communicates with a PC through a 50 foot RS 232 cable HAS part number CBL50 Connect the RJ45 end of the cable to the jack on the NetAXS panel The cable is used to provide communication to a single panel A second cable can be used with another NetAXS control panel connected to a second COM communication port which would enable eight readers to be used see Figure 11 RS 232 Configurati...

Page 33: ... configures a Gateway The panel must be power cycled for a new switch setting to be recognized DIP switch positions 1 5 are used to select the panel s address on the network Refer to Table 5 for DIP switch setting information Connectors J36 and J37 are provided for supplying biasing and end of line termination for the RS 485 network The board ships with all jumpers open For a multidrop RS 485 line...

Page 34: ...ateway NetAXS Panel NS2 Panel COM1 N1000 III N1000 IV RS 485 Multidrop Line N 485 PCI 2 3 A combination of N1000 III N1000 IV NS2 and NewAXS panels supporting a total of 31 panels per multidrop line Terminal NetAXS NetAXS Gateway NS2 COM1 NetAXS RS 485 Multidrop Line A combination of NetAXS and NS2 panels supporting a total of 31 panels per multidrop line Terminal ...

Page 35: ...terface see Figure 14 Ethernet TCP IP Configuration The Ethernet TCP IP interface provides 10 100 Mbit Ethernet support for each panel Up to 31 panels can be configured on each TCP IP connection NetAXS NetAXS Gateway NS2 NetAXS RS 485 Multidrop Line A combination of NetAXS and NS2 panels supporting a total of 31 panels per multidrop line Ethernet Up to 255 TCP IP Connections per System Network Int...

Page 36: ...36 www honeywell com NetAXS NX4L1 Installation Guide Installation Figure 15 shows the location of the panel s unique MAC ID Figure 15 Ethernet MAC Address Location Label with Ethernet MAC Address ...

Page 37: ...lation NetAXS NX4L1 Access Control Unit Installation Guide Document 7 901099V3 37 4 8 DIP Switch Settings Figure 16 locates the NX4L1 DIP switch panel and the J36 and J37 jumpers Figure 16 DIP Switch and Jumper Location J36 J37 DIP Switches ...

Page 38: ...f on off Address 9 off on off on off Address 10 on on off on off Address 11 off off on on off Address 12 on off on on off Address 13 off on on on off Address 14 on on on on off Address 15 off off off off on Address 16 on off off off on Address 17 off on off off on Address 18 on on off off on Address 19 off off on off on Address 20 on off on off on Address 21 off on on off on Address 22 on on on of...

Page 39: ...dedicated RS 485 Downstream Input Output I O bus A maximum of two NX4IN and a maximum of four NX4OUT for a total of six NX4IN OUT modules can be added to the downstream bus An NX4IN module has 32 supervised four state inputs that are limited to 2 200 ohms resistance The NX4OUT has two supervised inputs and 16 SPDT relay outputs Each input is limited to 2 200 ohms resistance Refer to the individual...

Page 40: ... For some installations the noise immunity improves if the NetAXS common is connected to the 24 V Return wiring for the downstream modules This connection is not needed for most installations Jumper settings JP1 CLOSED if the module is the last module on the downstream bus OPEN if the module is not the last module on the downstream bus JP2 any setting JP3 any setting JP4 NORMAL Positions 1 and 2 N...

Page 41: ...B5 1 TB5 4 TB5 6 TB5 9 TB5 2 TB5 3 TB5 7 TB5 8 TB5 1 TB5 4 TB5 6 TB5 9 TB5 2 TB5 3 TB5 7 TB5 8 TB5 1 TB5 4 TB5 6 TB5 9 TB5 1 TB5 7 TB5 8 TB5 4 TB5 6 TB5 9 EXTERNAL 24 VDC POWER SUPPLY NETAXS PANEL NX4IN JP1 OFF ADDRESS 1 NX4IN JP1 OFF ADDRESS 2 NX4OUT JP1 OFF ADDRESS 3 NX4OUT JP1 OFF ADDRESS 4 NX4OUT JP1 OFF ADDRESS 5 NX4OUT JP1 OFF ADDRESS 6 DEFAULT DOWNSTREAM I O SYSTEM CONFIGURATIONWITH COMMUNI...

Page 42: ...lation and programming of the NetAXS panel Figure 18 RS 485 Connection via PCI 2 COM Port It is recommended to Earth Ground EG each NetAXS enclosure individually RS 485 Cable RS485 NetAXS Panels Red White Black Green RS 485 COM TB7 1 RS485 TB7 2 RS485 TB7 3 RS485 COM 4 000 ft 1 200 m max 24 AWG 2 twisted pairs with shield 120 ohm 23 pf HAS part no NCP2441 TN Refer to N 485 PCI NS2 NS2 Access Contr...

Page 43: ... RS 485 Connection via NetAXS COM Port NetAXS Panel NetAXS Panel EG EG EG EG DIP Switch Settings S1 S5 Panel Address S6 ON J36 CLOSED J37 CLOSED DIP Switch Settings S1 S5 Panel Address S6 OFF J36 CLOSED J37 CLOSED DIP Switch Settings S1 S5 Panel Address S6 OFF J36 OPEN J37 OPEN It is recommended to Earth Ground EG each NetAXS enclosure individually RS 485 Cable NetAXS Panel TB7 1 RS485 TB7 2 RS485...

Page 44: ... S6 OFF J36 OPEN J37 OPEN It is recommended to Earth Ground EG each NetAXS enclosure individual Refer to NetAXS NetAXS Panel Connection Detail diagram NetAXS Panel EG EG DIP Switch Settings S1 S5 Panel Address S6 OFF J36 CLOSED J37 CLOSED NetAXS Gateway See RS 485 Cable Only Earth Ground EG one side of cable NetAXS Panel EG EG DIP Switch Settings S1 S5 Panel Address S6 OFF J36 OPEN J37 OPEN NetAXS...

Page 45: ... Refer to N 485 PCI 2 NetAXS Access Controller Panel Connection Detail diagram DIP Switch Settings S1 ON S2 ON S3 ON S4 ON S5 ON S6 ON Ack Nak Enable S7 ON S8 OFF 19 200 Baud See RS 485 Cable NetAXS Panel EG EG DIP Switch Settings S1 S5 Panel Address S6 OFF J36 CLOSED J37 CLOSED EG Only Earth Ground EG one side of cable RS 485 4 000 ft RS 232 50 ft max N 485 PCI h G d EG NetAXS Panel EG DIP Switch...

Page 46: ...ay panel appear in this section only to illustrate the installation and programming of the NetAXS panel Figure 22 RS 232 Connection CBL50 RS 232 50 ft max CBL50 RS 232 50 ft max DIP Switch Settings S1 S5 Panel Address NetAXS Panel NetAXS Panel It is recommended to Earth Ground EG each NetAXS enclosure individually Request To Send RTS Signal Ground GND Receive Data RXD Transmit Data TXD Clear To Se...

Page 47: ... NIC NetAXS Panel It is recommended to Earth Ground EG each NetAXS enclosure individually HUB SWITCH 100BaseT CAT5 328 ft max Crossover Cable 100BaseT CAT5 328 ft max 100BaseT CAT5 328 ft max HUB SWITCH HUB SWITC NetAXS Panel EG EG DIP Switch Settings S1 S5 Panel Address S6 ON Gateway NetAXS Panel EG NetAXS Panel EG DIP Switch Settings S1 S5 Panel Address S6 OFF NetAXS Panel EG NetAXS Panel EG DIP...

Page 48: ...witch Settings S1 S5 Panel Address S6 OFF J36 CLOSED J37 CLOSED DIP Switch Settings S1 S5 Panel Address S6 OFF J36 OPEN J37 OPEN It is recommended to Earth Ground EG each NetAXS enclosure individually Refer to 485 PCI 2 NetAXS Panel Connection Detail diagram Only Earth Ground EG one side of cable N 485 PCI 2 100BaseT CAT5 328 ft max LANSRLU1 RJ 45 RS 232 50 ft EG See RS 485 Cable Note HUB SWITCH R...

Page 49: ...TR CONTROL RX RX TX TX GROUND DN DIS RTSIDTR CONTROL S2 Loopback S2 Loopback J1 RS 232 Connector SHM B ASYNCH Short Haul Modem 5279 9 ft NetAXS Panel EG NetAXS Panel EG It is recommended to Earth Ground EG each NetAXS enclosure individually RS 232 50 ft max Male 9 Pin Male 25 Pin EG EG Only Earth Ground EG one side of cable See RS 485 cable note DIP Switch Settings S1 S5 Panel Address S6 OFF J36 O...

Page 50: ...S RTSIDTR CONTROL RX RX TX TX GROUND DN DIS RTSIDTR CONTROL S2 Loopback S2 Loopback J1 RS 232 Connector SHM B ASYNCH Short Haul Modem 5279 9 ft NetAXS Panel EG NetAXS Panel EG NetAXS Panel It is recommended to Earth Ground EG each NetAXS enclosure individually RS 232 50 ft max Male 9 Pin Male 25 Pin EG EG Only Earth Ground EG one side of cable See RS 485 cable note DIP Switch Settings S1 S5 Panel ...

Page 51: ... DCE DB 9 Straight Null 2 TX 2 TX 2 RX 3 RX 3 RX or 3 TX 5 Comm 7 GND 7 GND RS232 Cable MODEM PC DTE DCE DB 9 Straight Null 2 TX 2 TX 2 RX 3 RX 3 RX or 3 TX 5 Comm 7 GND 7 GND SHM B ASYNCH Short Haul Modem DEC DTE DN DIS RTSIDTR CONTROL RX RX TX TX GROUND DN DIS RTSIDTR CONTROL S2 Loopback S2 Loopback J1 RS 232 Connector DEC DTE SHM B ASYNCH Short Haul Modem 5279 9 ft NetAXS Panel EG DIP Switch Se...

Page 52: ...ED DIP Switch Settings S1 S5 Panel Address S6 OFF J36 OPEN J37 OPEN It is recommended to Earth Ground EG each NetAXS enclosure Individually Analog Phone Line Dedicated analog phone line recommended Remote DIP Switch Settings 1 3 8 ON 2 4 5 6 7 OFF Remote DIP Switch Settings 1 3 8 ON 2 4 5 6 7 OFF RS 232 50 ft RS 485 4 000 ft See RS 485 Cable Note DB 9 DB 25 Connectors Female Male 1 13 14 25 1 13 1...

Page 53: ...Switch Settings S1 S5 Panel Address S6 OFF J36 CLOSED J37 CLOSED DIP Switch Settings S1 S5 Panel Address S6 OFF J36 OPEN J37 OPEN It is recommended to Earth Ground EG each NetAXS enclosure Individually Analog Phone Line Dedicated analog phone line recommended Remote DIP Switch Settings 1 3 8 ON 2 4 5 6 7 OFF Remote DIP Switch Settings 1 3 8 ON 2 4 5 6 7 OFF RS 232 50 ft RS 485 4 000 ft See RS 485 ...

Page 54: ...le 10 000 ft max NetAXS Panel TB1 3 RS485 COM TB1 1 RS485 TB1 2 RS485 RS 485 Drain Wire to earth ground RS 485 Drain Only Earth Ground EG one side of cable RS 485 Drain not connected here connected at panel side RS 485 Drain Wire Floating N 485 PCI 2 NetAXS Panel NetAXS Panel NetAXS Panel RXD PWR TXD RS 485 Comm RS 485 Positive RS 485 Negative Fiber RXD Fiber TXD RXD PWR TXD RS 485 Comm RS 485 Pos...

Page 55: ...1 RS485 TB1 2 RS485 NetAXS Panel TB1 3 RS485 COM TB1 1 RS485 TB1 2 RS485 NetAXS Panel TB1 3 RS485 COM TB1 1 RS485 TB1 2 RS485 NetAXS Panel TB1 3 RS485 COM TB1 1 RS485 TB1 2 RS485 RS 485 Drain Wire to earth ground RS 485 Drain not connected here connected at panel side RS 485 Drain Wire Floating NetAXS Panel NetAXS Panel NetAXS Panel NetAXS Panel RXD PWR TXD RS 485 Comm RS 485 Positive RS 485 Negat...

Page 56: ...itchSettings S1 ON S2 ON S3 ON S4 ON S5 ON S6 ON S7 ON S8 OFF DIPSwitchSettings S1 S5 PanelAddress S6 OFF J36 CLOSED J37 CLOSED DIPSwitchSettings S1 S5 PanelAddress S6 OFF J36 OPEN J37 OPEN 485InterfaceConnectionTypes RS 485 N 485 PCI 2 N 485 HUB 2 N 485 PCI 2L NetAXSPanel COMPort M 56KModem LANSRL100orLANSRLU1 NetAXS TB7 NetAXS TB7 B L A C K G R E E N RED WHITE C O M M O N Groundonlyone sideofcab...

Page 57: ...TCONNECTor GROUNDSHIELD ToSerialConnection DIPSwitchSettings S1 S5 PanelAddress S6 OFF J36 CLOSED J37 CLOSED DIPSwitchSettings S1 S5 PanelAddress S6 OFF J36 OPEN J37 OPEN DIPSwitchSettings S1 S5 PanelAddress S6 ON J36 CLOSED J37 CLOSED NetAXS TB7 NetAXS TB7 Groundonlyone sideofcableshield X Shield GroundShield 485 485 485 Common 4 000ft 1 200m max 24AWG 2twistedpairswith shield 120ohm 23pf NCIpart...

Page 58: ...s for the panel to complete the power up sequence When the board does initialize verify that the appropriate LEDs identified in the following figure are in accord with the descriptions in Table 7 on page 59 Figure 34 System Relay and Power LEDs Ethernet Host RS232 and Downstream Host RS485 RDR 1 RDR 2 Relays RLY Relays RLY PWR Power Run RDR RDR H485 LINK COM DS H232 Readers Readers ...

Page 59: ...no cable is attached Table 7 LED Status LED PWR RUN H485 H232 DS COM LINK RLY RDR GREEN Power OK RUN Heart Beat Multi drop Receive Data RS232 Receive Data Down stream Receive Data 100Mbit Link OK Relay Active Flash at read RED N A N A Trans mit Data Trans mit Data Trans mit Data N A N A N A N A AMBER N A N A TX RX Data TX RX Data TX RX Data N A TX RX Data N A N A OFF Power Off Mal function No Com ...

Page 60: ...puts is 600 mA Maximum current for any of the eight relay outputs on the HPACM8 is 2 A Maximum battery charge current for the two batteries wired in series is 700 mA Maximum combined current of the four reader outputs and the two auxiliary outputs is 600 mA Maximum combined current of the two auxiliary outputs is 500 mA if no readers are being used The HPACM8 total current including all outputs ca...

Page 61: ...on Type Description Maximum Panels Maximum Distance Feet Meters Direct to COM Port CBL50 RS 232 Cable 9 pin to RJ 45 1 50 15 N 485 PCI 2 RS 485 9 pin to CPU 31 4 000 1 220 Modems M 9600 LA LO N 485 PCI 2 Lease line Modem to RS 485 31 NA 4 000 NA 122 SHM B ASYNC N 485 PCI 2 Short haul Modem to RS 485 31 5 280 4 000 1 610 1 220 SHM B ASYNC CBL50 Short haul Modem to RS 232 1 5 280 50 1 610 15 M 56K N...

Page 62: ...ons 7 8 Reader Wiring Table 9 Reader Wiring Cable Specifications Description AWG Maximum Distance Feet Meters Readers NC1861 BL 6 Conductor Shielded 18 500 153 Alarm Input NC1821 GR Twisted Pair Shielded 18 2 000 610 Relay Outputs NC1821 GR Twisted Pair Shielded 18 2 000 610 ...

Page 63: ... Common Door1 Status IN 2 Door2 REX IN 3 Common Door2 Status IN 4 Aux 12 VDC Aux Common Relay 1 N O Relay 1 Com Relay 1 N C Relay 2 N O Relay 2 Com Relay 2 N C Relay 3 N O Relay 3 Com Relay 3 N C Relay 4 N O Relay 4 Com Relay 4 N C Expansion RS485í B Expansion RS485 A Buzzer OUT 17 Tamper IN 11 12 VDC Common D1 D0 LED OUT 13 Buzzer OUT 18 Tamper IN 12 12 VDC Common D1 D0 LED OUT 14 DR3 REX IN 5 Co...

Page 64: ... The NX4L1 power supply contains a non replaceable input power line fuse If this fuse opens the power supply must be replaced Use the following procedure to change the 4 A 250 V Bussmann type S500 or Littelfuse type 217 fuse in the power inlet terminal block WARNING Be sure to disconnect the AC power before removing the fuse holder from the power inlet terminal block WARNING To reduce the risk of ...

Page 65: ... the Host RS 485 terminal block and re apply the power The IP address is incorrectly set to verify the value If you are connecting directly to a computer instead of going through a router or hub use a cross over Ethernet cable The N1000 panels on the Multidrop bus do not report N1000 panels will not communicate to a NetAXS panel that is configured as a Gateway Replace all of the N1000 panels with ...

Page 66: ...difference between the RS 485 positive and negative terminals if the EOL network is on or off J36 and J37 10 0 Technical Support 10 1 Normal Support Hours Monday through Friday 7 00 a m to 7 00 p m Central Standard Time CST except company holidays 1 800 323 4576 10 2 Web For technical assistance please visit http www honeywellaccess com ...

Page 67: ...the particular reader input The card is valid when it is in the card database on the panel and the current time and date conforms to the time zone associated with the card If it is not a valid card the door relay remains locked 1 2 Door Egress Door Lock Door Status Operation 1 Activate the door egress input 2 The panel energizes the door relay associated with the particular door egress input for a...

Page 68: ...to place the panel into the Multidrop mode Use a personal computer s serial communications port COM1 or COM2 and a terminal emulation program to configure the NetAXS panel for normal operation 2 2 Communication Settings Baud Rate 115200 Data Bits 8 Parity None Stop Bits 1 Flow Control None 2 3 Emulation Settings Echo typed characters locally YES Line Delay 500 milliseconds 2 4 Verifying Communicat...

Page 69: ...ommand Adds or deletes cards from the panel 5 W command Program each input for either NO NC and supervised or non supervised operation 6 P command Sets interlocks between input points and or output points Note In all examples the underscore character _ indicates a space and CR indicates a carriage return 3 1 T Time Command _T pn_hh mm CR Variables pn panel number 1 31 hh hours 0 23 Military time m...

Page 70: ...of week setting is a hold over from an old command The panel using the mm dd yyyy information will automatically configure panel to the correct day of the week regardless of the setting selected in day of week But the command still requires a value to be entered in its place of 1 7 Example 1 _D 1_01 09 2007_5 CR This command would set panel 1 to a date of 1 9 2007 and to Tuesday as the day of the ...

Page 71: ... Holiday 2 9 Holiday 3 Note 00 00 is the earliest time possible and 23 59 is the latest time possible A single time zone cannot be made to span midnight through the use of extended commands we can simulate this For more information please seek the guidance of technical support Example 1 _L 5_10_08 00 17 00_1_2_3_4_5 CR This command would configure panel 5 to add a time zone entry to time zone numb...

Page 72: ...anel 6 to add a card entry of 12345 to the panels database that will be valid on reader 1 2 3 and 4 during the times and days specified by time zone 10 Example 2 _C 18_52989_120_1_3 CR This command would configure panel 18 to add a card entry of 52989 to the panels database that will be valid on reader 1 and 3 during the times and days specified by time zone 120 3 5 C Card Delete Command _C pn_cod...

Page 73: ...n NC Non supervised normally closed default Example _W 1_9_SO CR Input 9 has been programmed as supervised normally open on panel 1 3 7 P Interlock Command _P pn_I O_ number _I O number _ D E F N P _ D E F N P CR Parameters number for an input number the range is 1 96 for output 0 78 D De energize E Energize F Follow N No action P Pulse Example _P 1_I_5_O_3_E_D When Input 5 is triggered Output 3 e...

Page 74: ... Command Use this command only for a drop line panel using RS 232 in standalone mode _U panel name _ D E Parameters D Disable E Enable Example _U 30_D This disables the flow control on panel 30 and prevents the panel s buffers from filling After a hard reset of the panel the flow control is re enabled ...

Page 75: ...the default reader port to relay associations 4 2 Reader LED Outputs The Reader LED output defaults to toggle the card reader LED from Red to Green for two seconds when a valid card is presented No LED color change other then a possible momentary change depending on reader used occurs if the card is not in the database The following are the default reader LED port to output associations Reader Num...

Page 76: ...s 4 4 Door Egress Inputs The panel has a Request To Exit egress input for each door The default condition is a two state input configured as Normally Closed contact When the egress input is active the associated output relay will be active The following are the default egress input associations Tamper LED Reports as Tamper 1 Input 9 Tamper 2 Input 10 Tamper 3 Input 11 Tamper 4 Input 12 Egress inpu...

Page 77: ...amper inputs The default condition is a two state input configured as Normally Closed Input 14 is a special case since it reports in as two inputs inputs 14 and 20 Input 14 can be used as a generic input but input 20 is used for the Enclosure Tamper alarm An active External Power Fail input indicates that the system is operating from the battery current not from the primary input power An inactive...

Page 78: ...eration NetAXS Panel Defaults 4 7 Additional Generic Outputs The panel has the following four additional generic form C relay outputs that can be programmed using the P command Relay output Controls 5 Output 5 6 Output 6 7 Output 7 8 Output 8 ...

Page 79: ...nd receive differential signal the 485 B is the negative side The COM or common is the signal ground The RS 485 COM signal is connected on the NetAXS controller but not on the NetAXS 123 controllers Note This signal RS 485 COM must NOT be connected to chassis GND When daisy chaining 485 ports together connect the 485 A wires from the upstream and downstream boards to the 485 A terminal and likewis...

Page 80: ...ops 3 0 RS 485 Wiring for NetAXS 4 Loop The 485 A of one controller is connected to 485 A of the next controller using one wire of the first twisted pair The 485 B of one controller is connected to 485 B of the next controller using the other wire of the first twisted pair On a loop that contains all NetAXS 4 controllers the 485 COM is connected The second pair of the wires are twisted together an...

Page 81: ...4 controller to the RS 485 COM of the next NetAXS 4 controller in the loop Do not connect the RS 485 COM on the NetAXS 123 controllers The RS 485 COM is bypassed on the NetAXS 123 controller The shield is only connected on one end of the cable not both See Figure B 3 on page 82 DO NOT CONNECT or GROUND SHIELD To Serial Connection DIP Switch Settings S1 S5 Panel Address S6 OFF J36 CLOSED J37 CLOSED...

Page 82: ...usually green and white are twisted together and connected to COM with the exception of the NetAXS 123 controller where the common is bypassed Note In the above figure the white wire is colored purple for easy viewing Ground Shield DO NOT CONNECT OR GROUND SHIELD DO NOT CONNECT OR GROUND SHIELD Ground Shield 1 2 3 485 A 485 B COM NetAXS 4 1 2 3 485 A 485 B COM NetAXS 4 VDC Out 485 A 485 B COM 24 V...

Page 83: ...ination By default the controllers are not terminated If the controller is the last one on the 485 bus then it should be terminated For more information see the controller s installation guide NetAXS 123 Place SW1 DIP switches 8 and 9 to the ON position to terminate NetAXIS Place jumpers across J36 and J37 to terminate ...

Page 84: ...84 www honeywell com End of Line Termination ...

Page 85: ......

Page 86: ...International Inc All rights reserved Specifications subject to change without notice Honeywell Access Systems 135 W Forest Hill Avenue Oak Creek WI 53154 1 800 323 4576 www honeywellaccess com Document 7 901099V3 ...

Reviews: