Sensitivity of the analog sensor at the
last calibration compared to
new sensor (only for analog sensors)
Display of the days differing from
the nominal maintenance date
(fixed value)
Days of operation since the last
calibration (fixed value)
Currently remaining days until
next maintenance date
(down counter)
Maximum measured current
value of the sensor head
8.10 Test Function for Relays
In this menu, the alarm relays can be manually turned on and off in order to test their function.
This menu is only available in special mode.
The manual operation takes priority over activation by a gas alarm. However, the external activation of the
alarm relays via a digital input takes priority over the manual test function.
The test mode simulates an alarm for the relay and the relay accepts the alarm status. The test function is
deleted by selecting "Automatic" or by exiting the Special Mode.
The testing is possible via code level 1, 3 and 4.
Selection of the relay 1 - 5
Selection of further
relays
Sensitivity
100%
Maintenance Days
Last xxx
Days of operation
Last xxx
Maintenance Days
Currently xxx
Max. Current Value
0
Relay
Test Function
Relay X
Status OFF
Relay 1
Alarm manual ON
Relay 1
Alarm manual OFF
Relay 1
Automatic