Symbol Description
Default Function
XXXX
Seconds
900
Time base for average calculation (range: 0
–
9999 sec.)
0 s
Seconds
120
Delay time in case of overlay by the current value (range: 0
–
9999
sec.)
0 ppm
Alarm
Threshold
100
Alarm threshold that triggers the overlay by the current value
(range: 0
–
999 ppm)
8.8.4 Power On Time
Gas sensors need a warm-up time, until the chemical process of the sensor reaches stable conditions. During
this running-in period the sensor signal can lead to an unwanted triggering of a pseudo alarm. Therefore, the
Power On time is started at each basic unit and each sensor head after power-on or voltage recovery. While
this time is running out, the
device is in special mode and doesn’t activate alarms. The Power On time appears
in the starting menu. During this phase the sensor head transmits "Warm-up time" instead of the measured
value.
The Power On Time of the individual components may be different. Only when the longest time has expired,
the system starts the measuring operation.
Symbol Description
Default Function
XX
Seconds
30
Power On time (range: 0
–
999 sec.)
8.8.5 Deadband
The unwanted noise of the measured value around the zero point, caused by the basic drift of the sensor, can
be suppressed by activating a deadband with a range of 0% to 15% of the measuring range depending on
device.
If the measured value is within the set % value, the display shows 0. Natural zero-point fluctuations of sensors
downwards or upwards can thus be suppressed in the display. Default setting 0 means deadband deactivated.
The suppression also affects the analog output, because the measured value must not assume a different
display depending on the output.
When opening the calibration mode, the deadband function switches off automatically.
Power On Time
30 s
Deadband
0 %