User Manual - PolyGard
®
2
Multi-Gas-Controller MGC2-K Honeywell
Page
26
PolyGard
®
is a registered trademark of MSR
GAMGC2-K_E_0320
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
Specification subject to change without notice
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
8.8 Menu System Parameters
8.8.1 System Information
Symbol
Description
Default
Function
XXXX
Serial Number
Serial number (factory set)
XX.XX.XX Date of Production
Date of production (factory set)
8.8.2 Maintenance Interval
Input of the maintenance interval in days. If you enter < 10 days, the function is not active
The maintenance interval can be set on the basic unit for maintenance information on the connected analog
inputs. If the maintenance interval is active, the accumulated maintenance message can only be acknowledged
by a calibration (at the analog input or at the head).
Symbol Description
Default Function
XXXX
Days
0
Maintenance interval (range: 10 - 2480 days)
8.8.3 Average Function
In the menu “Average Time” yo
u can define the time base for the calculation of the arithmetic average value
(30 measurements within the time base). This average value can be used for alarm evaluation as an alternative
to the current value. The selection which value should be used for evaluation is defined separately for each
alarm in the menu “
Alarm Threshol
d X”. In the average mode, the average value is indicated in the menu
“Measuring Values” next to the
current value.
The alarm evaluation of the operating mode “Average Value” is
overlaid by the current value, when the current
value exceeds the alarm thresh
old defined in the menu “AV
-
Overlay”. The overlay is delayed by the time factor
defined in this menu. The average overlay function is only available for the gas type CO.
System Parameters
Serial Number
XXXX
Mainten. Interval
XXXX Days
Date Manufacture
XX.XX.XX
Average Time
XXXX Sec.
AV - Overlay
0 s 0 ppm