ZX Fire Alarm Control Panels
MORLEY-IAS
Commissioning Manual
Document No. 996-175-000-1, Revision 01
Page 11
3.6 Overview
of
Menu
Structure
•
The commissioning menu options are presented in three different screens (Pages). When the
commissioning menu option is selected, the display will show:
PAGE 1
03-Mar-2007 11.38
All devices are inside working limits
1)CONFIGURE YES)More Options
[1]
2)Inspect 3)NORMAL OPERATION
•
To move between the three commissioning screens, press the ‘Yes’ key.
PAGE 2
03-Mar-2007 11.38
All devices are inside working limits
1)Time/Date 2)Program Integrity
[1]
3)Power Supplies
4)Passwords
PAGE 3
03-Mar-2007 11.38
All devices are inside working limits
1)Day Modes 2)Setup Options 3)Network
[1]
4)Events
Page
Option
Function
Configure
To configure the connection and operation of the signalling loop devices,
peripheral devices, sounder circuits and relay outputs.
Also provides configuration for upload / download of configuration data from
a PC.
Inspect
Provides the same functionality as the configure option but with view only.
This allows the data to be inspected without risking any inadvertent changes.
1
Normal Operation
To return the panel to normal operation – Level 2.
Time / Date
To allow the date and time and other clock functions to be changed.
Also allows the system memory to be cleared to return the panel back to
factory default settings.
Program Integrity
To show the version of the software installed in the panel.
To show the status of the operating program and configuration memory.
Power Supplies
Shows the current state of the AC Mains and Battery supply conditions.
2
Passwords
To define the number of User Level 2 passwords.
To define the value of each Level 2 password.
To define the maximum time the panel will remain at Level 2, without any key
pressed, before inhibiting the keys and returning to Level 1 operation.