43-TV-25-30 Iss.6 GLO Aug 07 UK
201
Section 7: Firmware Options
Firmware Credit System
The credits system is a flexible way of changing the recorder features without having to up-
grade the firmware. Simply purchase a number of credits to cover your current and possibly
future requirements and the recorder is delivered with the credits loaded. The credit value
in each recorder is displayed in the Factory menu.
Select the Options button and by activating and de-activating the options in the credit list,
the recorder will change its functionality. Go from:
Main Menu > Configure > Setup > Edit >
General > Factory > Credits
.
Table 7.1 : Firmware Options
Firmware option
Credit
value
Description
Full Maths* (Note 1)
4
Full Maths - this can handle math expressions that can consist of expressions up to 100-charac-
ters in length.
Full Maths with
Scripting* (Notes 1&4)
6
A powerful multi-line scripting ability available to solve complex state based applications. Eg.
building an application for: “
If
.. X happens, then Y will happen,
else
.. Z will occur.
Events (Note 3)
6
Events are certain conditions or operations that can be set up and logged according to the time
and date of an occurrence. Subsequently events can be reviewed or displayed on a graph. The
Event Causes currently include: Alarms - Into/Out of and Alarm Ack, Totals - Start/Stop/Reset/
Reset and Start, Digital Input - ON/OFF/State Change, T/C Burnout, Scheduled - Once/Interval/
Specific Days/Month End, User Counters, Max/Mins - Reset, System - Power ON/Setup Change/
Internal Memory Low/Export Memory Low/FTP Memory Low, User Action - Mark Chart, Batch -
Start/Stop/Pause. The Event Effects currently include: Mark Chart, Logging - Start/Stop, Totaliser
- Start/Stop/Reset/Reset & Start, Digital Output - ON/OFF, Alarm Acknowledge - Single pen/Pen
group/All pens, Emails, Screen Change, Print Screen, Counters - Reset/Increment, Max/Min
(Reset), Chart Control-Pause/Stop/Resume/Clear/Prefill, Clear All Messages, Delayed Event,
Script Timers - Start/Stop/Reset/Reset & Start, Play Sound - Start/Stop, Display Alert, Reports,
Batch - Start/Stop/Pause.
Fast Scanning mode
(Note 4)
5
For fast processes, the scan rate and recording of the data can be set for up to 50 times per sec-
ond (20ms) for up to 8 inputs for the Minitrend QX and 16 inputs for the Multitrend SX.
Totalisers/
Sterilisation
calculation
(Note 1)
4
Each pen can be associated with a totaliser. Using extra pens, the totalised values can be dis-
played and recorded; multiple totals can be calculated out of the same variable (weekly, monthly,
etc.). The totaliser function can handle Fo and Po sterilisation calculation.
Custom Screens (Note 2)
4
Import custom built screens that have been created in Screen Designer.
Reports
3
Generate reports manually or using the event system to show daily/weekly/monthly Totals, Max/
Mins, Averages, Current Value. Messages, Message Lists - Alarm, System, Diagnostic, Security
& User, Counters, Digital Inputs, and Digital Outputs. Reports can be printed, e-mailed as an
attachment or exported to external media in RTF format.
Health Watch/
Maintenance
2
The recorder keeps track of important “life actions” for improved diagnostics and preventative
maintenance notification. Including Power cycles, Last powered up, Total On time, Total Off time,
Longest off time, Battery life left, Backlight life left at 100% brightness, Compact Flash insertions,
Hi/Lo CJC value (Hi & Lo temps), Analogue In last factory/user cal, Relay operations.
Print Support
2
Enables the printer option to print text from various screens using a standard PCL (Printer Com-
mand Language) printer, connected to the USB port or to the network
Batch/Groups
5
The Batch function allows the user to segment portions of data for further analysis. The Batch
function manages sections of data. Concurrent batches are now associated with a group of pens.
The pens with in each group will belong to the batch that is controlled by that group. Batches can
be controlled through the event system and batch markers are setup by the user and are used to
identify and analyse batches of data. Supports up to 6 concurrent batches.
Summary of Contents for Minitrend QX
Page 2: ...ii 43 TV 25 30 Iss 6 GLO Aug 07 UK User manual ...
Page 50: ...44 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 192: ...186 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 210: ...204 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 242: ...236 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 249: ...43 TV 25 30 Iss 6 GLO Aug 07 UK 243 Multitrend SX Recorder 14 15 32 46 50 30 31 35 36 28 55 ...
Page 250: ...244 43 TV 25 30 Iss 6 GLO Aug 07 UK 52 11 23 33 39 5 6 RS485 USB host Ethernet 1 2 3 4 ...
Page 254: ...248 43 TV 25 30 Iss 6 GLO Aug 07 UK eZtrend QXe Recorder 16 5 3 1 4 2 24 49 9 45 19 6 49 ...
Page 258: ...252 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 274: ...268 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 276: ...270 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 296: ...290 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 308: ...302 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 312: ...306 43 TV 25 30 Iss 6 GLO Aug 07 UK ...
Page 323: ......