Function
3 .14 Relay outputs RO 1 and RO 2 function
The function of digital outputs RO 1 and RO 2 can be adjusted using BCSoft.
Signal at RO 1 or RO 2
Further setting options
Remarks
CLOSED position
equal to =
greater than or equal to > =
equal to or less than < =
Low-fire rate position (low)
Intermediate position (middle)
OPEN position (high)
Freely programmable position
Minimum and maximum value [°,%]
Relay switches when valve between min. and max.
position
Faults and warnings
Reference switch drift > 5%
1)
Reference switch drift > 10%
1)
Reference switch does not open
1)
Reference switch does not close
1)
Internal temperature > 90°C
Analogue input IN < 4 mA
Service note
Faults are always signalled, warnings are signalled
depending on the selection in BCSoft (see Inputs/
Outputs, 54 (Warnings and faults)
Fault
Only faults are displayed
Manual mode
Device is in Manual mode
Ready
Relay drops out in the event of: faults (not in the event
of warnings), Manual mode, zero position check,
calibration, no mains voltage
None
Relay output has no function
1)
These warnings are displayed as positioning errors in BCSoft.