Function
3 .5 .11 3-stage operation with two digital inputs
Operating mode 11
In idle state (DI 1 and DI 2 with no signal), the actuator
is in “closed” position and the butterfly valve is closed.
If a signal is applied to DI 1 (DI 2 with no signal), the
butterfly valve moves to “low” position (ignition position
and low-fire rate position).
If a signal is applied to DI 2 (DI 1 with no signal), the
butterfly valve moves to “high” position for pre-purge.
If a signal is applied to DI 1 and DI 2, the butterfly valve
moves to “middle” position (high-fire rate).
DI 1/V1 DI 2/air valve IC 40 Position
Valve position
Off
Off
closed
Closed
On
Off
low
Ignition position/low-fire rate
On
On
middle
High-fire rate
Off
On
high
Pre-purge
Example of application, see page 8 (Staged control
Operating mode 11