background image

GB-3

D

GB

F

NL

I

E

DG..H, DG..N

p

S

 = SK

p

S

 = SK + 0.18 mbar p

S

 = SK - 0.18 mbar

DG 1,5I

p

S

 = SK

p

S

 = SK + 0.4 mbar

e.g. SK = 1.2: 

p

S

 = 1.2 + 0.4 = 

1.6 mbar

e.g. SK = -1.2:

p

S

 = -1.2 + 0.4 = 

-0.8 mbar

DG 12I

p

S

 = SK

p

S

 = SK + 0.5 mbar

e.g. SK = 5: 

p

S

 = 5 + 0.5 = 

5.5 mbar

e.g. SK = -10:

p

S

 = -10 + 0.5 = 

-9.5 mbar

DG 18I, DG 120I, DG 450I

p

S

 = SK

DG 18I: 

p

S

 = SK + 0.5 mbar

e.g. SK = -10: 

p

S

 = -10 + 0.5 = 

-9.5 mbar

DG 120I, DG 450I: 

p

S

 = SK + 0.2 mbar

Connection facilities

2

1

3

4

and

 2

Gas, air, flue gas

and

 4

Air, flue gas

 

Ports 

 and 

4

 are suitable for air and flue gas only.

 

If the electrical contacts in the DG could be soiled 
by dirt particles in the surrounding air or in the 
medium, use a filter pad (see page 6 (Filter 
pad set)) at port 

/

4

. On IP 65 units, the filter pad 

is fitted as standard, see type label.

 1 

  Disconnect the system from the electrical power 

supply.

  

 Shut off the gas supply.

  

 Ensure that the pipeline is clean.

 4 

 Purge the pipe.

Installing DG..H, DG..N
Positive pressure measurement at port 1

 5 

 Seal port 

.

1

2

Rp 1/4

1

2

p

max

 =

Rp 1/4

2

Rp 1/4

0

Positive pressure measurement at port 
 5 

 Seal port 

1

.

1

2

Rp 1/4

1

2

p

max

 =

Rp 1/4

2

Rp 1/4

0

Negative pressure measurement at port 4
 5 

 Seal port 

.

3

Rp 1/8

4

3

4

Rp 1/8

3

0

Negative pressure measurement at port 
 5 

 Seal port 

4

.

3

Rp 1/8

4

3

4

Rp 1/8

3

0

Differential pressure measurement

 

Use port 

1

 or 

 for the higher absolute pressure 

and port 

 or 

4

 for the lower absolute pressure.

 5 

 Seal the remaining ports.

1

3

3

1

Installing DG..I

 

It is recommended that the port which is best 
protected from dirt and water be left open.

Summary of Contents for Krom Schroder DG H Series

Page 1: ...tes possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 11 17 The following chapters have been changed Adjustment Technical da...

Page 2: ... Installation CAUTION Please observe the following to ensure that the DG is not damaged during installation and operation Continuous operation with gases containing more than 0 1 by vol H2S or ozone concentrations exceeding 200 µg m accelerate the ageing of elastomer materials and reduce the service life Dropping the device can cause permanent dam age In this event replace the entire device and as...

Page 3: ...et at port 3 4 On IP 65 units the filter pad is fitted as standard see type label 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Ensure that the pipeline is clean 4 Purge the pipe Installing DG H DG N Positive pressure measurement at port 1 5 Seal port 2 1 2 Rp 1 4 1 2 0 Positive pressure measurement at port 2 5 Seal port 1 1 Rp 1 2 pmax Rp 1 4 2 Rp 1 4 0 Nega...

Page 4: ...maged during opera tion note the switching capacity see page 7 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend using an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF R 22 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Page 5: ...essure and pos sible reset Mean switching differential at min and max set ting Deviation from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Air pressure switches Deviation DG H N I 15 DG 1 5I 15 or 0 4 mbar DG 12I 15 or 0 5 mbar DG 18I 15 or 0 5 mbar If the DG does not trip at the desired switch ing point correct the adjusting range using the hand wheel Relieve th...

Page 6: ...tion of condensation the cover with pressure equalization element can be used The diaphragm in the screw connector is designed to ventilate the cover without allowing water to enter Order No 74923391 Restrictor orifice In the case of high pressure fluctuations we recom mend using a restrictor orifice contains non ferrous metals R Rp Hole diameter 0 2 mm Order No 75456321 hole diameter 0 3 mm Order...

Page 7: ...of the elastomer ma terials and reduces the service life please contact manufacturer Enclosure IP 54 or IP 65 Safety class 1 This unit is not suitable for cleaning with a high pressure cleaner and or cleaning products Mechanical data Gas type natural gas town gas LPG gaseous flue gas biogas max 0 1 by vol H2S and air Max inlet pressure pmax withstand pressure see page 5 Adjustment Max test pressur...

Page 8: ...ithout delay Check that the delivery is complete see page 2 Part designations Storage Storage temperature see page 7 Technical data Storage is subject to the ambient conditions de scribed Storage time 6 months before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is ...

Reviews: