BCU 580 · Edition 11.15l
54
Parameters
10 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name
Parameter
Value range
Description
Factory default
settings
Burner 1 FS1 flame signal switch-off
01
0 – 20
Burner 1 FS1 flame signal switch-off threshold in
µ
A
2
(5 when P04 = 1)
Burner 2 flame signal switch-off
02
0 – 20
Burner 2 FS2 flame signal switch-off threshold in
µ
A
2
(5 when P04 = 1)
04
0
1
2
3
4
5
6
7
8
Ionization
UVS
UVD
Ionization1 and UVS 2
Ionization1 and UVD 2
UVS 1 and ionization 2
UVD 1 and UVD 2
UVD 1 and ionization 2
UVD 1 and UVS 2
0
06
0
2
3
Off
Intermittent operation with UVS
Continuous operation with ionization/UVD
0
07
1
2
3
1 start-up attempt
2 start-up attempts
3 start-up attempts
1
08
1
2
3
1 start-up attempt
2 start-up attempts
3 start-up attempts
1
09
0
1
2
3
4
5
6
Off
Burner 1
Burner 2
Burner 1 and burner 2
Max. 5 × in 15 min. for burner 1
Max. 5 × in 15 min. for burner 2
Max. 5 × in 15 min. for burner 1 and burner 2
0
19
0; 1; 2
Time in seconds
1
▼