BCU 580 · Edition 11.15l
48
Profinet
7 .2 .2 Indexes for acyclic communication
With the help of acyclic communication between the
PLC (IO controller) and BCU/FCU (IO devices), it is pos-
sible to read information on parameters, statistics and
fault history on an event basis (e.g. using system func-
tion block Siemens FSB 52 RDREC).
The available data records differ in terms of their in-
dexes.
Index
Description
1001
Parameter
1002
Device statistics, counter
1003
Device statistics, faults/warnings
1004
Operator statistics, counter
1005
Operator statistics, faults/warnings
1006
Fault history
1007
Power module statistics
The contents and description of the indexes are de-