Honeywell IS-215T Installation Instructions Download Page 1

  Select the mounting location.

  Wire the unit.

  Mount the unit.

Mounting Location Guidelines

• 2.3 m (7’6”) mounting height
• Avoid direct or reflected sunlight
• Aim sensor away from windows or heating/

cooling devices

• Sensor must have a clear line-of-sight to

protected area

 

Push outward on the

PCB latch and lift the
PCB out of the hous-
ing.

 

Slide the wire through the wire channel and wire

access in the back housing.

 

Mount the back housing flat against a wall or in a

corner.

 

Replace the PCB.

 

Connect wires as shown using 0.64 - 1.63 mm

2

(14 to 22 AWG) wire size.  Observe proper
polarity.

Corner
Mount

Wire Channel

Wall Mount

IS

-215T P

assive Infrared Motion Sensor Installation Instructions

Separate the sensor housings and re-
move the printed circuit board (PCB).

Corner
Mount

Wiring Knockouts

POWER

12VDC

10mA

ALARM

16VDC

90mA

TAMPER

30VDC

0.5A

Configure the sensor sensitivity.

 

Configure the IS-215T for the sensitivity best

suited to the application.

ON

OFF

SENSITIVITY

SWITCH SW2 POSITION

High (pulse count 1)

Low [Normal] (pulse count 2)

Walk-test the sensor.

High Sensitivity:  2-4 Steps

(Pulse Count 1)

Switch

 

Use a small screwdriver to

push in the housing latch
at the bottom of the sensor,
and gently pull apart the
housings.

Alarm
LED

Low [Normal] Sensitivity:  3-5 Steps

(Pulse Count 2)