Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9-15
9.5.3
Point Programming For Internal or External Power Module
(RPS-1000)
To program for an internal or external power module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 for available choices, then
press ENTER.
5.
Enter the number of the circuit or point you wish to edit, then press ENTER.
6.
Select the type by pressing the up or down arrow key, then press ENTER.
7.
Select the function by pressing the up or down arrow key, then press ENTER.
8.
If the point supports latching press the up or down arrow key to select latching or non-latching, then press
ENTER.
9.
Select the zone or group by pressing the up or down arrow key, then press ENTER.
10. If the point supports not being supervised, press the up or down arrow key to select supervised or non-super
-
vised, then press ENTER.
11. Press ENTER to edit point name. See Appendix B. Or, Press right arrow key to skip point name edit.
12. Repeat Steps 1 through 11 for all circuits.
RELAY
OUTPUT PT
Select Group
Output point, a general use relay type. Use for applications requiring a
relay, such as fan shutdown, elevator recall, and so on.
AUX RESET
Use for auxiliary power, resettable applications. See Section 4.15.5.3
for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if you
were using an auxiliary power supply for door holders, you would use
this option. See Section 4.15.5.1 for a description of how this option
operates.
Detector
2-Wire Smoke
W-Gateway
Wireless Gateway
W-SWITCH
Same as SWITCH
W-Relay
Same as Relay
When a wireless relay is in use, module device count must be limited to
109 modules per loop. This includes wired and wireless modules that
are on the same loop. The module address must be within 1-109.
Table 9-6: Menu choices for Internal/External Power Module
Choices
Type Selections
Function
Selections for
each Type
Comments
Enter Point
Table 9-5: Programming Options for 6815 Modules
Type
Selection
Function
Latching Option
Comments