• HPR2416UL • HPR2416CBUL
CCTV Rack Mount Power Supply/Distribution Units
PN 52992:A 5/23/06 ECN 07-005
Honeywell
12 Clintonville Road
Northford, CT 06472
http://www.honeywellpower.com
Product Installation Document
1 Overview
These Honeywell Rack Mount CCTV power supplies will provide 24 VAC power distributed via 16 circuits for powering
CCTV cameras and other video equipment. Each circuit will be fuse protected at 3.0A, or PTC protected at 2.5A. Fuses
are accessible directly through the front panel by removing six screws.
2 Specifications
•
Input: 117VAC, 60Hz, 2A.
•
Output: 8A @ 24VAC (200VA).
•
Maximum current rating:
– HPR2416UL: any output, 3A; total supply, 8A @ 24VAC**.
– HPR2416CBUL: any output, 2.5A*; total supply, 8A @ 24VAC**.
* PTC Protected Class 2 Power Limited Outputs.
** Outputs 1 to 8 provide 4A @ 24VAC (100VA).
** Outputs 9 to 16 provide 4A @ 24VAC (100VA).
•
16 outputs.
•
Surge and transient protection.
•
Transformer has built-in thermal protection.
•
Indicator Lights:
– Input Power Indicator (1 red): Illuminated power switch/circuit breaker.
– Output Power LEDs (16 green): ON indicates that AC is present at the related output circuit.
•
Overload Protection:
– Input power switch has built-in circuit breaker.
– AC line fuse (5 x 20mm glass).
– Individual output circuits have a glass fuse (5 x 20mm) or resettable PTCs.
– NOTE: To reset a PTC that has experienced an overload or short circuit, switch power off for 5 minutes to allow
the PTC to reset itself.
•
Factory installed three-conductor AC line cord.
•
Unit maintains camera synchronization.
•
2U rack chassis for use in standard EIA 19” rack.
•
Removable rear terminal blocks.
•
Line power rocker switch with built-in circuit breaker indicates power on with red neon lamp.
•
Designed for quick installation.
•
Maximum Temperature Range: 32°F to 120°F (0°C to 49°C); for indoor use only
!
WARNING:TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE
THIS APPLIANCE TO RAIN OR MOISTURE.
For continuous protection against hazard, replace fuses only with exact type and rating. All 117V wiring should be
routed so that it cannot touch 24V wiring; minimum spacing 3/8” (0.953cm). This installation should be made by a
qualified service person and should confirm to all local codes. Install in accordance with the National Electrical
Code.