HPFF12 NAC Expander —
P/N 53576:B 11/24/2010
35
Section 3: Programming Options
This section describes the programming options available via DIP switch settings. The HPFF can
be field-programmed using DIP switch SW1 on the Control circuit board. Refer to the following
illustration for switch location and DIP switch settings for ON and OFF positions.
Figure 3.1 Field-Programming DIP Switches
3.1 DIP Switch Settings
The following table lists the programmable features and the switch settings required to select a
particular feature. A detailed description of each is presented in the following pages.
Switches 2-7
shown in OFF position
Switch 1
shown in ON position
HP
FF8
12
-sw1
.wmf
SW1 DIP Switch
1
SIG 1/2 “A”
2
SIG 1/2 “A”
1 OFF, 2 OFF
= Pass-through (of Steady On, sync, or coded; DO NOT use with full-wave rectified input).
1 ON, 2 OFF
= Temporal.
1 OFF, 2 ON
= Sync generator (see switches 5 & 6).
1 ON, 2 ON
= Pass-through Filtered (use for full-wave rectified inputs).
3
SIG 3/4 “B”
4
SIG 3/4 “B”
3 OFF, 4 OFF
= Pass-through (of Steady On, sync, or coded; DO NOT use with full-wave rectified input).
3 ON, 4 OFF
= Temporal.
3 OFF, 4 ON
= Sync generator (see switches 5 & 6).
3 ON, 4 ON
= Pass-through Filtered (use for full-wave rectified inputs).
5
SYN SEL “B”
6
SYN SEL “A”
5 OFF, 6 OFF
= Cooper Wheelock
5 ON, 6 OFF
= System Sensor
5 OFF, 6 ON
= Amseco and Faraday
5 ON, 6 ON
= Gentex
7
AC 2HR
OFF
- No delay in Trouble reporting with an AC failure.
ON
- 2 hour delay in Trouble reporting with an AC failure.
See Sections 3.2.3 and 3.2.4 for further details of TB2 immediate AC Fail and programmed
no delay/delayed Trouble contacts.
8
SIG SEL
This switch works in conjunction with the initiating device signal input(s) and switches 1 through 6 to
determine General Alarm*, Split Alarm**, or Silencing***.
8 ON
= Split Alarm**
• NAC outputs 1 and 2 are controlled by Signal Input 1.
• NAC outputs 3 and 4 are controlled by Signal Input 2.
8 OFF, Signal Input 1 ON, Signal Input 2 ON
= General Alarm* on all four NAC outputs.
8 OFF, Signal Input 1 ON, Signal Input 2 OFF
= Silencing*** of all four NAC outputs.
*
General Alarm
is visual strobe and audible horn activation.
**
Split Alarm
is Signal Input I controlling NAC outputs 1 and 2, and Signal Input 2 controlling NAC outputs
3 and 4.
***Silencing
is visual strobe activation but audible horn is silenced for the initiating device.
Table 3.1 DIP Switch Settings