INSTALLATION INSTRUCTIONS

HE260A,B

Bypass Flow-Through Humidifier

READ AND SAVE THESE INSTRUCTIONS

APPLICATION

The HE260A,B Bypass Flow-Through Humidifier uses the warm air furnace
blower to provide humidification for the whole house. The HE260A,B works
with virtually any Honeywell humidity control, but for optimal performance,
use with the Honeywell Perfect Climate Comfort Center™ control.

INSTALLATION

WARNING

Hazardous Voltage.
Can cause Personal Injury or Equipment Damage.
Do not cut or drill into any air conditioning or electrical accessory.

CAUTION

Freezing Water and High Water or Static Pressure Hazard.
Can cause water damage or permanent equipment damage.

The humidifier must be located where the ambient temperature is
above 32

°

F (0

°

C) and below 160

°

F (71

°

C).

Be sure supply plenum static pressure is no greater than 0.3 in.
w.c. and water pressure is no greater than 125 psi.

IMPORTANT

To assure optimal product performance, be sure the template is
level before marking.

1. Determine the best location for the humidifier and draw a level line on

the plenum. See Fig. 1.

IMPORTANT

Mount the humidifier at least 3 in. (76 mm) above the furnace jacket
to allow adequate space for the solenoid valve and drain line. Check
that there is adequate space above the humidifier to remove and
install the humidifier cover. Do not install on a furnace jacket.

M12304

WATER 
FEED NOZZLE

HUMIDIFIER 
PAD ASSEMBLY

FRAME

HUMIDIFIER 
HOUSING

SIDEWALL

BYPASS SIDEWALL

COVER

WATER 
FEED TUBE

M12248B

HORIZONTAL

DOWN

FLO

LOWBOY

HIGHBOY

Fig. 1. Typical humidifier installation locations.

2. Tape the template in position and trace around the template.
3. Remove the template and carefully cut the rectangular opening.
4. Disassemble the humidifier; remove the cover and take out the

humidifier pad assembly. See Fig. 2.

NOTE:

Sidewalls are interchangeable for either left or right
bypass installation. To change direction, remove the screws
holding each sidewall, switch sidewall locations and reinstall
the screws.

5. Position the humidifier housing in the opening (be sure it is level), so

the locking tabs are in place on the lower sheet metal edge of the
opening.

6. Secure the humidifier housing to the opening at the top and bottom

using sheet metal screws.

Fig. 2. Humidifier components.

7. Locate the other plenum and cut an opening for a 6 in. (152 mm) collar.
8. Install the 6 in. (152 mm) collar.

NOTE:

Be sure to install a duct damper for summer shutoff on
systems with air conditioning.

9. Install a 6 in. (152 mm) diameter duct from the collar to the humidifier.

NOTE:

Some installations require a 90

°

 elbow attachment to the

collar.

10. Seal the duct connections with duct tape.

NOTE:

To avoid sagging and stress on the humidifier, add support
when ducting is longer than 4 ft (120 cm).

TEMPLATE

69-1106EF-3

Summary of Contents for HE260A

Page 1: ...is adequate space above the humidifier to remove and install the humidifier cover Do not install on a furnace jacket M12304 WATER FEED NOZZLE HUMIDIFIER PAD ASSEMBLY FRAME HUMIDIFIER HOUSING SIDEWALL BYPASS SIDEWALL COVER WATER FEED TUBE M12248B HORIZONTAL DOWN FLO LOWBOY HIGHBOY Fig 1 Typical humidifier installation locations 2 Tape the template in position and trace around the template 3 Remove ...

Page 2: ... saddle valve included to tap into the water supply line at an appropriate location CAUTION Chemical Hazard Can cause personal injury or equipment damage Do not use any line connected to an air conditioner IMPORTANT The saddle valve is not designed to regulate water flow The valve is either open or closed To prevent debris from clogging the solenoid in line filter be sure to install the saddle val...

Page 3: ... FLO LOWBOY HIGHBOY Fig 1 Emplacements types de l humidificateur 69 1106EF 3 IMPORTANT Installer l humidificateur à une distance minimale de 76 mm 3 po au dessus du boîtier de l appareil de chauffage afin de laisser un espace suffisant pour le montage de l électrovanne et du tuyau de vidange S assurer qu il y a suffisamment d espace au dessus de l humidificateur pour enlever et remettre le couverc...

Page 4: ...t automatique il n y a pas lieu d installer un relais de détection de courant ou un interrupteur à ailette REMARQUE Certains modèles de ventilateurs ont des prises pour humidificateurs Si tel est le cas il n est pas nécessaire d installer un relais de détection de courant ou un interrupteur à ailette TUYAUTERIE DU ROBINET VANNE À ÉTRIER L humidificateur fonctionne avec de l eau dure ou de l eau do...

Reviews: