Honeywell GENT S4-710 Data And Installation Download Page 1

These instructions contain information on the S-Quad product
range. The S-Quad product integrates dual angle smoke, heat
and carbon monoxide gas detection with electronic sounder,
speech and LED flasher (Strobe) in one assembly.

Product range

All LPCB approved Sensor STATES are
listed in the

S-Quad Description and

commissioning information

.

Part number

Description

Symbol

S4-720

Heat Sensor

H

S4-780

Heat Sensor &
Sounder

HS

S4-720-ST-VO Heat Sensor, Speech

& Strobe

HStSp

S4-715 #

Optical Sensor #

O #

S4-710

Optical & Heat Sensor

OH

S4-770

Optical & Heat Sensor
plus Sounder

OHS

S4-770-ST

Optical & Heat Sensor
plus Strobe

OHSt

S4-711

Dual Optical & Heat
Sensor

O

2

H

S4-771

Dual Optical & Heat
Sensor plus Sounder

O

2

HS

S4-711-ST

Dual Optical & Heat
Sensor plus Strobe

O

2

HSt

S4-711-VO

Dual Optical & Heat
Sensor plus Speech

O

2

HSp

S4-711-ST-VO Dual Optical & Heat

Sensor plus Speech &
Strobe

O

2

HSpSt

S4-911

Dual Optical, Heat &
CO Sensor

O

2

HCO

S4-911-ST-VO Dual Optical, Heat &

CO Sensor plus
Speech & Strobe

O

2

HCOSpSt

# This 'Optical' Sensor is for use in Vigilon Compact system.

Associated products

S4-700

S-Quad Base

S4-FLUSH

Semi-Flush fixing kit

S4-COVER-DUST

Sensor dust cover (50 pack)

S4-COVER-BASE

Base dust cover (50 pack)

S4-EXTRACTOR

Removal tool

S4-COVER-REMOVER Dust cover remover tool

(spare adaptor)

S4-BASE-LABEL

Label plate (50 pack)

S4-BASE-GASKET

Base IP Gasket (50 pack)

General specification

Operating voltage

35V - 41V

Weight

110g (with base - 170g)
S4-720 only:88g (with base -
148g)

Dimensions

117mm diameter by 49.6mm
height (With base the height
increases to 63.8mm)

IP rating

IP30
IP20 when mounted on a metal
back box

Enclosure

ABS

Colour

RAL 9010

Approval

LPCB approved

Storage Temperature

-20

°

C to 70

°

C (for S-Quad

with CO -20

°

C to 50

°

C)

Ambient operating
temperature

-10

°

C to 50

°

C

Relative Humidity

95% non condensing
(5°C to 45°C)

Heat (H)

Standard

EN54 : Part 5 : 2002

Optical (O)

Standard

EN54 : Part 7 : 2000

Dual Optical (O

2

)

Standard

EN54 : Part 7 : 2000

Sounder (S)

Standard EN54 : Part 3 :

Gas (CO)

Standard *

LPS 1274

Multi sensor

standard CEA 4021

EN54-18 : 2005

EN54-17 : 2005
(section 4.8)
data:

V

max

42V

I

C max

0.4A

V

nom

40V

I

S max

1A

V

min

24V

I

L max

20

m

A

V

SO max

16V

Z

C max

0.1

W

V

SO min

8V

* The 'Gas' sensing is designed to meet the requirements

of LPS 1274 : issue 1.0

Information on minimum sound output levels to include polar
dispersion is covered in a technical note TECH7018.033,
available on request from manufacturer.

4188-779 issue 8-7_08/10_S-Quad _Part 1

1

Data and Installation

S-Quad

Sensor, Sounder, Speech & Strobe

by Honeywell

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for GENT S4-710

Page 1: ...SE Base dust cover 50 pack S4 EXTRACTOR Removal tool S4 COVER REMOVER Dust cover remover tool spare adaptor S4 BASE LABEL Label plate 50 pack S4 BASE GASKET Base IP Gasket 50 pack General specification Operating voltage 35V 41V Weight 110g with base 170g S4 720 only 88g with base 148g Dimensions 117mm diameter by 49 6mm height With base the height increases to 63 8mm IP rating IP30 IP20 when mount...

Page 2: ...ported for use with S Quad fire sensors The Slave units are only compatible with 34xxx range of fire sensors All S Quad devices can be configured as either monitored input or unmonitored output The factory setting of the programmable input output is unmonitored output to drive an external repeat LED without a series resistor There is a maximum cable length limit of 15 metres from the S Quad base t...

Page 3: ...se and S Quad will align To fit the dust cover using tool Place the dust cover onto the tool inside the cradle Offer the cover to the S Quad locate and push to fit it onto the assembly Withdraw the tool when the dust cover is in place To remove the dust cover using tool A dust cover remover tool must be fitted to the main tool to extract the dust cover Press the pad of the dust cover remover tool ...

Page 4: ...gislation 0832 Gent by Honeywell Hamilton Industrial Park 140 Waterside Road Leicester LE5 1TN UK Product EC Certification No of Conformity No S4 710 0832 CPD 0706 S4 711 VO 0832 CPD 0608 S4 715 0832 CPD 0707 S4 720 0832 CPD 0516 S4 720 ST VO 0832 CPD 0609 S4 771 0832 CPD 0511 S4 770 0832 CPD 0708 S4 780 0832 CPD 0517 S4 911 0832 CPD 0515 S4 911 ST VO 0832 CPD 0512 S4 711 0832 CPD 0513 S4 711 ST 0...

Reviews: