    FIRE Overrides MASS NOTIFICATION

SYSTEM   PRIORITY: (Select  One)                                                                                    

E3 SERIES

®

 Combination FIRE and MASS NOTIFICATION 

SYSTEM (ACU) Operation Instructions for 

FIRE Overrides MASS NOTIFICATION

NORMAL STANDBY CONDITION:

The “

AC POWER ON

” light is lit. The time displays on the 

panel display. All other lights & sounding devices are OFF.

FIRE ALARM OR CO ALARM CONDITION

:

In the event of an alarm condition, immediately notify 
Authorized Personnel.

FOR FIRE ALARMS

: On the NGA, the following occurs:

The red “

ALARM

” light flashes.

Identifies the source of the alarm.

Activates Fire Alarm A/V signaling devices.

FOR CO ALARMS

: On the NGA, the following occurs:

Backlight flashes on the NGA display.

Identifies the source of the alarm.

Activates the Alarm signals.

Sounds the panel sounding device.

FOLLOW PROPER EMERGENCY PROCEDURES TO 
NOTIFY THE FIRE DEPT., EVACUATE THE 

BUILDING ETC.

FOR A MASS NOTIFICATION CONDITION: 

When no fire 

condition exists, to initiate Mass Notification, select any 
recorded message or the MNS page enable. On the NGA, the 
following occurs:

Identifies the source of the MNS Alarm Event.

Activates the red “ALARM” LED.

Sounds the panel sounding device.

NOTE:

 The ACU overrides all LOC control with the activation 

of any ACU control function.

TO ACKNOWLEDGE FIRE, CO OR MNS ALARMS:

1.

Press the “

ALARM ACKNOWLEGE

” button to silence 

the sounder and stop the flashing of the ALARM LED 
(remains illuminated).

NOTE:

 You must Acknowledge each ALARM activation 

individually. To view multiple events, scroll the display.

TO SILENCE FIRE OR CO ALARM SIGNALING:

When instructed by Authorized Personnel, the audible Fire 
Alarm signals may be silenced.
1.

Press the 

“SIGNAL SILENCE”

 switch.

2.

A message, 

“SYSTEM SILENCED

,” appears on the 

display. 

NOTE:

 Mass Notification messages are not silenceable. 

Manually turn off the active message to silence. A reminder 
tone will sound every 30 seconds until you reset MNS.

TO RESET FIRE OR CO ALARMS:

1.

After the alarm condition is resolved, an Authorized 
Personnel may reset the system.

NOTE:

 Restore all initiating devices to normal or the system 

will not reset.
2.

To access the Reset screen, press 

RST

 on the 

touchscreen.

3.

Press the 

FIRE RESET

 button or Cancel.

NOTE: 

For Fire Overrides MNS, the 

FIRE

 event must be 

reset first. Then, reset the MNS condition.

TO RESET AN MNS Condition: 

1.

Reset the Fire event (if a Fire event exists).

2.

Reset the 

MNS

 condition.

3.

To access the Reset screen, press 

RST

 on the 

touchscreen.

4.

Press the 

MNS RESET

 button or Cancel.

LIVE VOICE PAGING DURING A FIRE CONDITION:

1.

Press the Page enable ASM button # 10 indicated by the 
green LED. 

2.

To activate the audio paging, press the push-to-talk 
microphone button.

3.

Page automatically overrides recorded messages and 
signal silence.

NOTE: 

THIS SYSTEM MUST BE TESTED REGULARLY IN 

ACCORDANCE WITH LOCAL AND STATE FIRE CODES.

MASS NOTIFICATION Overrides FIRE

   
             

E3 SERIES

® 

Combination FIRE and MASS NOTIFICATION 

SYSTEM (ACU) Operation Instructions for 

MASS NOTIFICATION Overrides FIRE

NORMAL STANDBY CONDITION:

The “

AC POWER ON”

 light is lit. The time displays on the 

panel display. All other lights & sounding devices are OFF.

MASS NOTIFICATION ALARM CONDITION: 

To initiate Mass Notification, select any recorded message or 
the MNS page enable.
On the NGA display, the following occurs: 

Identifies the source of the MNS Alarm Event.

Activates the red “ALARM” LED.

Sounds the panel sounding device.

Overrides any existing Fire A/V signaling devices.

NOTE:

 The ACU overrides all LOC control with the activation 

of any ACU control function.

FIRE ALARM OR CO ALARM CONDITION:

In the event of an alarm condition, immediately notify 
Authorized Personnel.

FOR FIRE ALARMS: 

On the NGA display, the following 

occurs:

The red “ALARM” light flashes.

Identifies the source of the FIRE Alarm Event.

Activates the Fire Alarm A/V signaling devices.

FOR CO ALARMS:

 The following occurs on the NGA.

Backlight flashes on the NGA display.

Identifies the source of the CO Alarm Event.

Activates the Alarm signals.

Sounds the panel sounding device.

TO ACKNOWLEDGE FIRE, CO OR MNS ALARMS:

1.

To silence the sounder and stop the flashing of the 
ALARM LED (remains illuminated), press the 

“ALARM 

ACKNOWLEDGE”

 button.

NOTE: 

You must Acknowledge each ALARM activation 

individually. To view multiple events, scroll the display.

TO SILENCE ALARM SIGNALING: 
NOTE:

 Mass Notification messages are not silenceable. 

Manually turn off the active message to silence. A reminder 
tone will sound every 30 seconds until you reset MNS.

TO SILENCE FIRE OR CO ALARM SIGNALING:

When instructed by Authorized Personnel, the audible Fire 
alarm signals may be silenced. 
1.

Press the “

SIGNAL SILENC

E” switch.

2.

A message, 

“SYSTEM SILENCED

,” appears on the 

display.

TO RESET AN MNS CONDITION: 

1.

Reset the 

MNS

 condition.

2.

Reset the 

Fire

 event (if a fire event exists).

3.

To access the Reset screen, press 

RST

 on the 

touchscreen.

4.

Press the 

MNS RESET

 button or Cancel.

TO RESET FIRE OR CO ALARMS:

1.

After you reset the MNS condition and resolve the alarm 
condition, an Authorized Personnel may reset the 
system.

NOTE: 

Restore all initiating devices to normal or the system 

will not reset.
2.

To access the Reset screen, press 

RST 

on the 

touchscreen.

3.

Press the 

FIRE RESET

 button or Cancel.

NOTE:

 For MNS Overrides Fire, the MNS event must be 

reset first. Then, reset the Fire condition.

LIVE VOICE PAGING DURING AN MNS CONDITION:

1.

Press the Page enable ASM button # 9 indicated by the 
green LED.

2.

To activate the audio paging, press the push-to-talk 
microphone button.

3.

Page automatically overrides recorded messages and  
signal silence. MNS Paging initiates an MNS ALARM 
event.