Honeywell Fire-lite ECC-LOC Product Installation Download Page 1

One Fire-Lite Place
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.firelite.com  

ECC-LOC Local Operator Console

Product Installation Document

PN LS10028-000FL-E:B   8/9/2013   13-696

1 Overview

The ECC-LOC is an optional Local Operator Console 
compatible with the ECC-50/100 Emergency Command 
Center. The ECC-LOC has a complete operator interface 
like the ECC-50/100 main console.  The LOC requires an 
external data bus connection, an external audio riser 
connection, and an external operator interface power 
connection (24 volts DC) from the ECC-50/100 main 
console.  Refer to the ECC-50/100 Manual #LS10001-
000FL-E for more information.

NOTE: Installation and wiring of this device must be 
done in accordance with NFPA 72 and local ordinances.

2 Specifications

Data Bus Input - TB3 - 1(B), 2(A) EIA-485 / 
Data Bus Output - TB4 - 1(B), 2(A) EIA-485

Operator Interface Power Input - TB3 - 3(+), 4 (-) / 
Operator Interface Power Output - TB4 - 3(+), 4(-)
– 24 VDC Nominal, Isolated

Audio Riser Input - TB5 - 3(-), 4(+) / 
Audio Riser Output - TB5 - 5(-), 6(+)
– Style Y (Class B) or Style Z (Class A) audio 

connections to external operator interface 
components

– Power-limited circuitry (Class 2), supervised
– Audio signal level: 3.85 V

RMS

, maximum

– Frequency range: 800 Hz - 2800 Hz

3 Cabinet Mounting

3.1  Removing the Dress Panel

1. Open the door and lift the door off the pin hinges.
2. Remove the two (2) screws securing the dress panel to 

the backbox.

3. Open the dress panel and disconnect the ground wire 

from the back.

4. Lift up dress panel and pull out lower pivot flange. 

Slide the upper pivot flange down to completely 
remove the dress panel from cabinet.  Store in a safe 
location.

 

3.2  Mounting the Backbox

1. Mark and predrill hole in the wall for the center top 

keyhole mounting bolt using the dimensions illus-
trated below.

2. Install center top fastener in the wall with the screw 

head protruding.

3. Place backbox over the top screw, level and secure.
4. Mark and drill the left and right upper and lower 

mounting holes.
Note: Outer holes (closest to sidewall) are used for 
16” O.C. stud mounting.

5. Install remaining fasteners and tighten. 
6. Carefully reinstall the dress panel by reversing the 

steps in Section 3.1.  Remember to reattach the 

ground cable.

7. Reinstall door.

A trim ring, TR-CE, is available for semi-flush mount 
installations.

 screw 

locations

Figure 1  Removing the Dress Panel

1. lift up

2. pull out

3. slide down

keyholes

12.0” (30.48cm) O.C.

lower mounting holes

Figure 2  Backbox Mounting

Summary of Contents for Fire-lite ECC-LOC

Page 1: ... circuitry Class 2 supervised Audio signal level 3 85 VRMS maximum Frequency range 800 Hz 2800 Hz 3 Cabinet Mounting 3 1 Removing the Dress Panel 1 Open the door and lift the door off the pin hinges 2 Remove the two 2 screws securing the dress panel to the backbox 3 Open the dress panel and disconnect the ground wire from the back 4 Lift up dress panel and pull out lower pivot flange Slide the upp...

Page 2: ...ect 1 24 Manually activates or deactivates speaker zones circuits Message Select 1 8 Manually activates or deactivates stored messages 8th button becomes a shift for messages 9 14 FIRE SYSTEM ACTIVE SYSTEM CONTROL ALL CALL 1 2 3 4 5 6 7 8 9 10 11 12 13 18 19 20 21 22 23 24 16 17 14 15 Figure 3 ECC LOC Keypad ecckyd wmf SPEAKER ZONE 1 SPEAKER ZONE 2 SPEAKER ZONE 3 SPEAKER ZONE 4 SPEAKER ZONE 5 SPEA...

Page 3: ...Yellow LED will turn on indicating a message trouble in the group of messages not currently being viewed Remote Amplifiers 1 8 Fault Yellow LED per remote amplifier that turns on steady when an amplifier has a fault LOC RPU RM 1 8 Fault Yellow LED per remote console that turns on steady when a remote console has a fault Green LED per remote console that turns on steady when a remote console is act...

Page 4: ...e Condition Activation of trouble signal under normal operation indicates a condition that requires immediate attention Contact your local service representative Silence the audible signal by pressing the TROUBLE SILENCE switch The trouble indicator will remain illuminated B A B A B A B A main control board LOC display board TB24 TB12 TB22 TB3 TB4 TB5 external operator interface power 24VDC extern...

Reviews: