IPDACT
IP Communicator
IPDACT Dm 371-I
Quick Start Programming Guide using a PC Serial Port
Model TS540/1
1
. Requirements
Alarm Panel
•
“Contact Id” compatible panel with tone dialing.
•
Existing PSTN Service (for backup communication lines).
•
PC with RS-232 serial port.
•
Console cable for the IPDACT.
Consumption
Idle
Alarm
Transient
IPDACT ver 2 (TS-540/X) (24V)
100mA
120mA
300mA
Internet Access
Either a static IP address (always the same) or a dynamic IP address (could be different every time
a connection is made) are possible.
2. Checklist
¹
a.
IPDACT console access password (default is 24680)
b.
Installer password, required to execute the register command.
c.
IP address, subnet mask and gateway for IPDACT
2
d.
IPDACT account number or client number.
e.
IP address, and UDP Port number of the VisorALARM central station
1
Please obtain the following information from your central monitoring station.
2
If you have a DHCP server in the network to which the IPDACT connects, these parameters can be obtained automatically.