88
MS-5UD & MS-10UD Series Manual —
P/N 52626:C2 1/24/2012
Programming
Master Programming Level
This screen shows the Input Zone that has been assigned to be the All-Call Zone. In this example,
Zone 1 is the All-Call Zone. The All-Call Zone can be changed by pressing the
1
key while view-
ing the ANN-AUDIO Options Screen. The following screens will be displayed.
These screens allow the programmer to select which Input Zone will be assigned as the All-Call
Zone.
ANN-SEC Enable
The ANN-SEC option must be enabled if any modules are connected to the ANN-SEC option card
at J13. To enable the Secondary ANN-BUS, press
2
while viewing ANN-BUS Screen #3 so that the
display reads
ANN-SEC ENABLE YES
. Each press of the
2
key will cause the display to toggle
between
ANN-SEC ENABLE YES
and
ANN-SEC ENABLE NO
. The factory default setting is
ANN-
SEC ENABLE NO
.
ANN-AUDIO ALL CALL
1=NO ALL CALL ZONE
2=INPUT ZONE 1
3=INPUT ZONE 2
All-Call Options Screen #1
ANN-AUDIO ALL CALL
1=INPUT ZONE 3
2=INPUT ZONE 4
3=INPUT ZONE 5
All-Call Options Screen #2
ANN-AUDIO ALL CALL
1=INPUT ZONE 9
2=INPUT ZONE 10
All-Call Options Screen #4
(MS-10UD
Only
)
ANN-AUDIO ALL CALL
1=INPUT ZONE 6
2=INPUT ZONE 7
3=INPUT ZONE 8
All-Call Options Screen #3
(MS-10UD
Only
)