82
MS-5UD & MS-10UD Series Manual —
P/N 52626:C2 1/24/2012
Programming
Master Programming Level
ANN-BUS
Pressing
1
while viewing the Option Modules screen will cause the control panel to display the fol-
lowing screens.
A variety of ANN-BUS option modules can be installed in the FACP. These devices communicate
with the FACP over the ANN-BUS terminals on the control panel.
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press
1
while viewing ANN-BUS screen #1 so that the display reads
ANN-
BUS Enabled Yes.
Each press of the
1
key will cause the display to toggle between
ANN-BUS
Enabled Yes
and
ANN-BUS Enabled No
.
BUS Modules
If an ANN-BUS module is installed, press
2
while viewing ANN-BUS screen #1 to select ANN-
BUS addresses for the module(s). The following screen will be displayed.
ANN-BUS
1=BUS ENABLED NO
2=BUS MODULES
3=AUTO CONFIGURE
ANN-BUS Screen #1
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
3=ANN-RLY OPTIONS
ANN-BUS Screen #2
ANN-BUS
1=ANN-AUDIO OPTIONS
2=ANN-SEC ENABLE NO
ANN-BUS Screen #3
ANN-BUS MODULES
1=ADDR. 1 NONE
2=ADDR. 2 NONE
3=ADDR. 3 NONE
On Board DACT Screen #1