116
MS-5UD & MS-10UD Series Manual —
P/N 52626:C2 1/24/2012
Operating Instructions
Hazard/Tornado Condition Operation
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history bufferActivate appropriate LED on the ANN-LED annunciator (required
for this application)
Note that, like supervisories, process monitor signals latch, except when programmed for process
monitor autoresettable.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado operation is intended for Manual activation.
Hazard/Tornado Condition operation will initiate the following events:
•
The piezo sounder pulses ¼ second On, ¼ second Off
•
The LCD displays a hazard message along with the device name, type, adjective/noun,
associated zones and time/date
•
Communicate the hazard condition to the Central Station (if the default event code has been
changed from 000 to a reportable event code)
•
Relays programmed for hazard will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history bufferActivate appropriate LED on the ANN-LED annunciator (required
for this application)
Hazard conditions latch.
4.9 Medical Alert Condition Operation
Medical alert operation is:
•
not intended for nurse call stations (applications) per UL1069.
•
not intended for signaling professional medical staff.
•
to be used for summoning security guards or other trained personnel within the facility
•
intended for Manual activation.
Medical Alert Condition operation will initiate the following events:
•
The piezo sounder ¼ second On, ¼ second Off
•
The LCD displays a medical alert message along with the device name, type, adjective/noun,
associated zones and time/date
•
Communicate the medical alert condition to the Central Station (if the default event code has
been changed from 000 to a reportable event code)
•
Relays programmed for medical alert will be activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history bufferActivate appropriate LED on the ANN-LED annunciator (required
for this application)
Medical alert conditions latch.