96
ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
Programming
Master Programming Level
The Acknowledge Button Enable
(ACK BTN ENABLE)
option allows the programmer to select whether the Ack/Step button on any installed
ANN-80 or ANN-100 annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-80/100 Options Screen
#1 causes the display to toggle between
Ack Btn Enable Yes
(Ack/Step button functions normally) and
Ack Btn Enable No
(Ack/Step button
never functions). In Canadian mode, the FACP cannot be controlled by the ANN-100 so the Reset feature is unavailable. This option is
called
STEP ENABLE
in Canadian mode. Enabling the Step feature will allow the user to scroll through events on the screen.
The Silence Button Enable
(SIL BTN ENABLE)
option allows the programmer to select whether the Silence button on any installed ANN-80
or ANN-100 annunciator will function normally or always be ignored. Pressing
1
while viewing the ANN-80/100 Options Screen #2 causes
the display to toggle between
Sil Btn Enable Yes
(Silence button functions normally) and
Sil Btn Enable No
(Silence button never functions).
The Reset Button Enable (
RST BTN ENABLE
) option allows the programmer to select whether the Reset button on any installed ANN-80 or
ANN-100 annunciator will function normally or always be ignored. Pressing
2
while viewing the ANN-80/100 Options Screen #2 causes the
display to toggle between
Rst Btn Enable Yes
(Reset button functions normally) and
Rst Btn Enable No
(Reset button never functions). In
Canadian mode, the Reset feature is unavailable. The programming option will change to
LMP BTN ENABLE
in Canadian applications.
Pressing
2
while viewing the ANN-80/100 Options Screen #2 causes the display to toggle between
Lmp Btn Enable Yes
(the ANN-100 will
perform a local test of all LEDs) and
Lmp Btn Enable No
.
The Drill Button Enable (
DRL BTN ENABLE
) option allows the programmer to select whether the Drill button on any installed ANN-80 or
ANN-100 annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-80/100 Options Screen #2 causes the
display to toggle between
Drl Btn Enable Yes
(Drill button functions normally) and
Drl Btn Enable No
(Drill button never functions). In
Canadian mode, the Drill feature is unavailable. The programming option will change to
SND BTN ENABLE
in Canadian applications.
Pressing
3
while viewing the ANN-80/100 Options Screen #2 causes the display to toggle between
Snd Btn Enable Yes
(the ANN-100 will
perform a test of its local sounder by turning it on for 5 seconds) and
Snd Btn Enable No
.
Key Control Enable
(Canadian Mode Only)
The Key Control feature is only available when the FACP is in Canadian mode of operation. Canadian mode
usually limits the functionality of annunciators. Enabling key control allows annuciator key presses to be pro-
cessed normally. To enable the annunciator Key Control, press
1
while viewing ANN-BUS Options screen #2
so that the display reads
Key Ctrl Enabled Y.
Each press of the
1
key will cause the display to toggle between
Key Ctrl Enabled Y
and
Key Ctrl Enabled N
.
3.5.9 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by selecting
the Password Change option. Pressing
1
while viewing Programming Screen #4 will cause the following screen
to be displayed:
Press
1
to change the Master Programming Level password,
2
to change the Maintenance Level password or
3
to change the Remote Down-
load password.
Note that the passwords will not be displayed on LCD annunciators.
The following screen will appear when any change option is selected:
A flashing cursor will appear in the center of the display. Enter a new eight digit password (such as 10101010 for the Master Level). After
the eighth digit is entered, the following screen will be displayed:
Re-enter the new password to accept the change. The display will return to the initial Password Change Screen.
Invalid Password
If a password is entered incorrectly, the panel will display
Invalid Message
and a code.
XXX ANN-BUS
1=KEY CTRL ENABLED
ANN-BUS Options Screen #2
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
Password Change Screen
ENTER NEW EIGHT DIGIT
PASSWORD
44444444
Enter Password Screen
VERIFY NEW PASSWORD
44444444
Password Change Screen
INVALID PASSWORD
44444444444444444444
Invalid Password Screen