ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
69
Master Programming Level
Programming
Pressing
2
for System Setup, while viewing Programming Screen #2, will cause the following screens to be dis-
played:
Function Keys
The ES-50X keypad has 4 programmable function keys. These keys can be programmed to allow rapid disable/enable of various fire panel
inputs and outputs during scheduled maintenance. Pressing any function key results in a trouble signal at the panel. Pressing
1
on System
Setup Screen #1 displays the following:
Select
1
,
2
,
3
, or
4
to program the corresponding Function Key. The following screens display for each Function
Key where “(X)” represents the number of the key chosen.
To Enable or Disable the Function Key, press the
1
key while viewing the Function Keys Screen #1. Each press of the key will toggle the
screen between
Key Enabled Yes
and
Key Enabled No
.
Pressing
2
key while viewing the Function Keys Screen #1 allows the user to select individual zones that the Function Key will control.
Pressing
3
assigns all zones to the selected Function Key.
Each function key can be assigned to control any of the 2 onboard NAC circuits on the ES-50X. By pressing the
2
key while viewing the
Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing
1
or
2
toggles the screen between
Yes
(controlled by function key) and
No
(not controlled by function key) for each onboard NAC
circuit.
The Remote Synchronization (TB8 on the FACP’s main circuit board) can also be disabled through program-
ming of a function key. To disable remote synchronization, press the
3
key while viewing the Function Keys
Screen #2. Each press of the key will toggle the screen between
Rem Sync Disb Yes
and
Rem Sync Disb No
.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by using
the Banner option. Pressing
2
while viewing System Setup Screen #1 will cause the following to be displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NACS
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=CHARGER ENAB NO
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
FUNCTION KEYS
1=F1 3=F3
2=F2 4=F4
Function Keys Screen
FUNCTION KEYS
1=F1 3=F3
2=F2 4=F4
Function Keys Screen
Function Keys Screen #1
Function Keys Screen #2
F(X) KEY OPERATION
1=KEY ENABLED NO
2=ZONES
3=ALL ZONES
F(X) KEY OPERATION
1=NACS
2=DIS REM DISB NO
F(X) NACS
1=NAC 1 N 2=NAC 2 Y
Function Keys Screen
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB NO
Function Keys Screen #2
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen