ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
55
Master Programming Level
Programming
If the selected detector is a multi-criteria detector, the following screen will display respectively before the Zone Assignment Screen allow-
ing the user to program the zones independently.
Wireless
The Wireless selection will update automatically if the system recognizes a wireless device. A wireless device
operates as part of the SWIFT® wireless network. If the detector is wireless, the display reads
Wireless Yes
. If
the device is wired, the display will read
Wireless No
. Fore more information on the SWIFT wireless network,
refer to the SWIFT manual
, #LS10036-000FL-E.
Sounder Base
The Sounder Base selection allows the programmer to enter different values if the selected detector is mounted in an addressable sounder
base. Pressing
2
while viewing Edit Detector Screen #5 will display the following:
If the selected detector has been installed in a sounder base, press
1
while viewing Sounder Base Screen #1 until the display reads
Installed
Yes
. Each press of the
1
key will cause the display to toggle between
Installed Yes
and
Installed No
.
The Silenceable selection allows the programmer to select whether the selected sounder base can be silenced, either by pressing the Alarm
Silence key or by enabling Autosilence. Pressing the
2
key while viewing Sounder Base Screen #1 will enable the Silenceable feature caus-
ing the display to read
Silenceable Yes
. Repeated presses of the
2
key will cause the display to toggle between
Silenceable Yes
and
Silence-
able No
. When set to Canadian mode of operation, a third silenceable option appears, Silenceable Auto. When set to
Silenceable Auto
, the
intelligent sounder base will automatically silence after the Control Module Auto Silence timer expires.
The Fire Coding feature allows the programmer to select the type of output that the sounder base will generate when activated. Pressing
3
while viewing Sounder Base Screen #1 will cause the following displays to appear:
The programmer can select the sounder base output by pressing the number corresponding to the desired output. The coding selections are:
•
Steady - a continuous output with no coding
•
Temporal 3 - ½ Second On, ½ Second Off, ½ Second On, ½ Second Off, ½ Second On, 1½ Seconds Off
•
Temporal 4 - ½ Second On, ½ Second Off, ½ Second On, ½ Second Off, ½ Second On, ½ Second Off, ½ Second On, 1½ Seconds Off
The sounder base volume has two settings: Low, or High. Press
1
while viewing Sounder Base Screen #2 until
the display reads Low or High as desired. Each press of the
1
key will cause the display to toggle between
Vol-
ume Low
and
Volume High
.
A maximum of five zones can be programmed to each sounder base. Pressing
2
while viewing Sounder Base
Screen #2 displays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first
0
to the left. Enter the three digit number corresponding to the zone that is to be
assigned to this sounder base. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones
EDIT DETECTOR
1=PHOTO ZONES
2=HEAT ZONES
3=CO ZONES
Multi-Criteria Detector Zones Screen
EDIT DETECTOR
WIRELESS NO
2=SOUNDER BASE
Edit Detector Screen #5
Edit Detector Screen #5
SOUNDER BASE
1=INSTALLED NO
2=SILENCEABLE NO
3=CODING STEADY
Sounder Base Screen #1
SOUNDER BASE
1=ZONE ASSIGNMENT
000 000 000 000 000
2=VOLUME LOW
Sounder Base Screen #2
CODING
1=STEADY
2=TEMP-3
3=TEMP-4
Coding Screen #1
SOUNDER BASE
1=ZONE ASSIGNMENT
444
444
444
444
444
2=VOLUME LOW
Sounder Base Screen #2
ZONE ASSIGNMENT
Z
444
Z
444
Z
444
Z
444
Zone Assignment Screen